EasyManua.ls Logo

Signet 8900 - 11.1 Relay Setup Menu

Signet 8900
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33 Signet 8900 Multi-Parameter
11.1 Relay Setup Menu
Relay 1 Source:
Flow F1 >
Select measurement type or derived function to be assigned to this relay:
Level, Volume, Temperature, Pressure, Flow, pH, ORP, Difference, Ratio,
Conductivity, None, Sum, Reject, Passage, Recovery A, Recovery B, Recovery C,
Power 2, Power 4, Multiple.
Select the mode of operation for this relay:
Off, Low, High, Window, Prop Pulse, PWM, Volumetric Pulse, USP, Advanced.
If relay mode is Low or High: Enter the relay setpoint.
If relay mode is Prop Pulse, PWM or Window: Enter the low-end setpoint.
If relay mode is Prop Pulse, PWM or Window: Enter the high-end setpoint.
If relay mode is PWM, set the pulse period.
Minimum 0.1 s, maximum 1000 s (16.7 minutes)
Relay 1 Rng: max
+45.000 GPM >
Relay 1 Mode:
Low >
Relay 1 SetPnt:
10.0 GPM >
Relay 1 Rng: min
+25.000 GPM >
Relay 1 Period:
5.0 secs >
Relay 1 Delay:
1.0 sec >
Relay 1 maxRate:
120 pls/min >
Relay 1 Volume:
100.00 Gallons >
Relay 1 P.Width:
0.1 secs >
Relay 1 Logic:
N.O. >
Test Relay 1:
>
If relay mode is High, Low, Window or USP: Enter hysteresis.
If relay mode is High, Low, Window or USP: Enter the trigger time delay. The relay will
activate only if the process value exceeds the setpoint for this period of time.
Minimum 0.1 s, maximum 6400 s (106.67 minutes)
If relay mode is Pulse: Set the maximum pulse rate. (1 to 400 pulses per minute.)
If relay mode is Vol Pulse (Flow): Set the volume represented by one pulse.
If Relay mode is pulse: Set the duration of the relay pulse.
Minimum 0.1 s, maximum 999.9 s (16.66 minutes)
For solid state relays only: N.C. = Normally Closed
N.O. = Normally Open
Manually toggle relay to test operation.
Relay 1 Hys:
5.0 GPM >

Table of Contents