2.6.1  Separate 
ducts kit 
(fig. 9)
The diagrams of Figure 9 show a few exam-
ples of the permitted exhausts configura-
tions.
2.6.2  Connection to existing flues
The ø 80 or ø 60 exhaust pipe can also be
connected to existing flues. When the boiler
runs at low temperature, it is possible to use
standard flues provided that:
- The flue is not be used by other boilers.
- The interior of the flue is protected to pre
-
vent a direct contact with condensation
from the boiler. The products of combu-
stion must be conveyed through a flexible
or rigid plastic pipe around 100 to 150
mm in diameter, and condensation must
be siphoned off at the foot of the pipe. The
277, 5
67,5
169
148
112
134
236
CS
CA
CA
119
222
ø 80
ø 60
Fig. 7
KEY
CA Inlet
CS Outlet
Example of allowable installation vers. “25” calculation in that the sum of the head
losses of the single fittings is less than 7.6 mm H
2
O:
  
Inlet
  
Outlet
9
m horizontal pipe
ø 80 x 0.15 1.35
9
m horizontal pipe
ø 80 x 0.15 1.35
n° 2
90° elbows
ø 80 x 0.20 0.40
n° 2
90° elbows
ø 80 x 0.25 0.50
n° 1 terminal ø 80 0.10 0.25
Total head loss
1.85 + 2.10 =3.95 
mm H
2
O
Fig. 8
TABLE 1 - ACCESSORIES ø 80
Accessories ø 80 Total head loss (
mm H
2
O)
12  25  30  35
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Coaxial duct kit
90° elbow MF 0.05 0.10 0.20 0.25 0.25 0.30 0.30 0.40
45° elbow MF 0.05 0.05 0.15 0.15 0.20 0.20 0.25 0.25
Extension L. 1000 (horizontal) 0.05 0.05 0.15 0.15 0.20 0.20 0.25 0.25
Extension L. 1000 (vertical) 0.05 0.05 0.15 0.15 0.20 0.20 0.25 0.25
Wall terminal 0.05 0.15 0.10 0.25 0.10 0.35 0.15 0.50
Wall coaxial exhaust
*
Roof outlet terminal * 0.25 0.05 0.80 0.10 1.10 0.15 1.50 0.20
* The loss of the accessorie in aspiration concludes the collector code 8091400/01
TABLE 1/a - ACCESSORIES ø 60
Accessories ø 60 Total head loss (
mm H
2
O)
12  25  30  35
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Coaxial duct kit 1.25 0.25 2.50 0.50 2.50 0.50 2.50 0.50
90° elbow MF 0.15 0.40 0.40 0.90 0.50 1.10 0.60 1.40
45° elbow MF 0.10 0.25 0.35 0.70 0.45 0.90 0.55 1.20
Extension L. 1000 (horizontal) 0.10 0.40 0.40 0.90 0.50 1.10 0.60 1.40
Extension L. 1000 (vertical) 0.10 0.30 0.40 0.60 0.50 0.70 0.60 0.80
Wall terminal 0.15 0.70 0.50 1.20 0.80 1.40 1.10 1.60
Wall coaxial exhaust
*
Roof outlet terminal * 0.25 0.05 0.80 0.10 1.10 0.15 1.50 0.20
* The loss of the accessorie in aspiration concludes the collector code 8091400/01
OPERAZIONE DA ESEGUIRE
SOLO NEL MONTAGGIO DEL
KIT Ø 80 COD. 8089912
A
B
4
1
3
2
6
4
5
C
A
B
4
1
3
2
ASSEMBLY OF THE KIT ø 80 code 8089912/ø 60 code 8089913
KEY
1 ø 125 Gasket
2 Fumes exhausts
flange with tap
3 Fastening screw
4 ø 108 Gasket
5 Suction collar (only for
kit code 8089913)
6 MF ø 60 reduction (only
for kit code 8089913)
OPERATIONS REQUIRED
ONLY FOR THE ASSEMBLY
OF THE ø 80 KIT CODE
8089912

Other manuals for Sime MURELLE HE ErP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sime MURELLE HE ErP Series and is the answer not in the manual?

Sime MURELLE HE ErP Series Specifications

General IconGeneral
BrandSime
ModelMURELLE HE ErP Series
CategoryBoiler
LanguageEnglish

Related product manuals