4
1
TB1 TB2 TB3
2 3 4 5 6 7 8
LED
AP 120 GND NEUNO C NC-
TEST24V
1 2 3 4 5 6
LED
AP-
TEST
SEE NOTE 2
SEE NOTE 3
NOT USED
24 VDC OR 24 VAC
POWER SOURCE
FUSED
4098-9842
DUCT CONTROL STATION
1 2 3 3 4 5
UNIT
BEING
CONTROLLED
TURNS OFF (OPEN CONTACTS)
ON ALARM OR DETECTOR REMOVAL
OR LOSS OF POWER
4098-9687
STAND ALONE
DUCT DETECTOR
Figure 2. Wiring the 4098-9687 Stand Alone Duct Detector for 24 VDC or 24 VAC Operation
Continued on next page
Electrical Specifications, Continued
Notes:
1. Stand Alone Duct Detector wiring is 12 to 18 AWG.
2. Maximum allowable wire run from Stand Alone Duct
to Duct Control Station is 500 feet.
3. All relay contacts rated 5 amp at 24 VDC/VAC; or
120 VAC resistive non-power-limited.