Installation Instructions
2005, 2008, 2009, 2011 SimplexGrinnell LP. All rights reserved.
Specifications and other information shown were current as of publication and are subject to change without notice.
Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its affiliates and are used under license.
579-246
Rev. K
This publication describes the installation procedure for the following 4100-Series System Power
Supplies (SPS) and Remote Power Supplies (RPS):
4100-5111/5112 SPS (120 VAC) (mounts to expansion bays only)
4100-5125/5126 RPS (120 VAC)
4100-5113 SPS (220/230/240 VAC) (mounts to expansion bays only)
4100-5127 RPS (220/230/240 VAC)
These products are compatible with 4100U and 4100ES Fire Alarm Control Panels
(FACP).
IMPORTANT:
The SPS described in this document are not physically the same as the SPS
used in the CPU bay.
Verify FACP System Programmer, Executive, and Slave Software compatibility
when installing, or replacing system components. Refer to the Technical
Support Information and Downloads website for compatibility information.
This publication discusses the following topics:
Topic See Page #
Cautions and Warnings 2
Introduction to the SPS and RPS 3
Mounting 7
Configuring the SPS and RPS 8
Internal Wiring 10
NAC Field Wiring 12
IDNet Field Wiring (SPS only) 23
Auxiliary Power Wiring 26
Auxiliary Relay Wiring 29
Troubleshooting 31
City and relay connections can be made from the SPS (the RPS supports relay connections only).
Refer to the City and Relay Card Installation Instructions (574-839) to install a relay card to the
SPS, or a city card to the SPS or RPS.
To find out more about the CPU bay version of the SPS, which operates in the same way as the
expansion bay version of the SPS but mounts differently, refer to the 4100ES Fire Alarm System
Installation Guide (574-848).
For information on Expansion Power Supplies (XPS), refer to XPS and XNAC Installation
Instructions (574-772).
Introduction
In this Publication
Related
Documentation
firealarmresources.com
Question and Answer IconNeed help?

Do you have a question about the Simplex 4100-5112 SPS and is the answer not in the manual?

Simplex 4100-5112 SPS Specifications

General IconGeneral
BrandSimplex
Model4100-5112 SPS
CategoryPower Supply
LanguageEnglish

Summary

Safety and Compliance

General Cautions and Warnings

Important precautions regarding product handling, electrical safety, and static discharge.

SPS;RPS Overview

SPS;RPS Electrical Specifications

SPS;RPS Mounting Procedure

SPS;RPS Configuration

Jumper and DIP Switch Settings

Details on jumper settings (P1, P2, P3) and DIP switch configuration for addressing.

Card Address Configuration Table

Internal Wiring - Power Distribution

PDM Module Connections

Detailed steps for wiring AC power and batteries to the PDM and SPS/RPS.

Internal Wiring - Module Connections

NAC Field Wiring Overview

NAC Field Wiring - Class B Tables

NAC Field Wiring Guidelines

Compatible NAC Appliances

NAC Appliance Rating Guidelines

Class A NAC Wiring Details

Class B NAC Wiring Details

IDNet Field Wiring (SPS Only)

IDNet Wiring Guidelines

General guidelines for IDNet wiring, including power, supervision, and distance limits.

IDNet Class A Wiring

IDNet Class B Wiring

Auxiliary Power Wiring

Auxiliary Power Guidelines

Details on using dedicated terminals or NACs for auxiliary power and device compatibility.

Auxiliary Relay Wiring

Troubleshooting SPS;RPS Issues

Common Trouble Messages and Causes

Lists and explains messages like AC Power Loss, NAC Miswired, and Earth Faults.