1 LT0638 Iss 1.1 7/2017
READ AND SAVE THESE INSTRUCTIONS - Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and
associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED - Upon
unpacking your Simplex product, inspect the contents of the carton for shipping damage.
If damage is apparent, immediately le a claim with the carrier and notify an authorised
Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical eld power when making any internal
adjustments or repairs. All repairs should be performed by a representative or authorised
agent of your local Simplex product supplier.
STATIC HAZARD - Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components
• Prior to installation, keep components wrapped in anti-static material at all times
SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To ensure proper
system operation, this product must be tested in accordance with AS1670.1, after any
programming operation or change in site-specic software. Reacceptance testing is
required after any change, addition or deletion of system components, or after any
modication, repair or adjustment to system hardware or wiring. All components, circuits,
system operations, or software functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not inadvertently affected, at least
10% of initiating devices that are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system operation veried.
The 4100-6077AU MX Digital Loop Card is a 4 x 10 inch (double-height) PDI module
that interfaces a single MX Digital Loop to the 4100ESi re panel.
Features:
4 x 10 inch double-height PDI module
• Interfaces MX Loop to 4100ESi
Supports up to 250 MX devices
500mA Loop power
Electrically isolated MX Loop with earth fault monitoring
Cautions and
Warnings
Introduction
4100-6077AU
MX Digital Loop Card
Installation Instructions
This publication discusses the following topics:
Topic Page
Introduction to the MX Digital Loop Card 2
Installing the MX Digital Loop Card 4
Conguring the MX Digital Loop Card 6
Wiring the MX Digital Loop Card to Addressable Devices 8
Compatible MX Addressable Devices 10
In this
publication

Other manuals for Simplex 4100ESi

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ESi and is the answer not in the manual?

Simplex 4100ESi Specifications

General IconGeneral
BrandSimplex
Model4100ESi
CategoryFire Alarms
LanguageEnglish

Related product manuals