EasyManuals Logo

Simplex 4100U Installation Instructions

Simplex 4100U
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
4100U Remote Annunciators
Installation Instructions
© 2006 Tyco Safety Products Westminster, Westminster, MA 01441-0001 USA
All specifications and other information shown were current as of document revision date, and are subject to change without notice.
Tyco, Simplex, and the Simplex logo are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries.
579-271
Rev. G
This publication describes the installation procedures for the following PIDs:
4100-9607 Remote Annunciator w/ Flexible User Interface – Domestic
4100-9608 Remote Annunciator w/ Flexible User Interface - Canadian
4100-9609 Remote Annunciator w/ Flexible User Interface - International
4100-9610 Remote Annunciator
4100-9611 Basic Remote Annunciator
4100-9612 Basic Remote Annunciator w/ Flexible User Interface - Domestic
4100-9613 Basic Remote Annunciator w/ Flexible User Interface - Canadian
4100-9614. Basic Remote Annunciator w/ Flexible User Interface - International
IMPORTANT: Verify 4100U system programmer, executive, and slave software
compatibility when installing or replacing system components. Refer to
solution bulletin SB01014 for compatibility information.
Upon unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an authorized Simplex
product supplier.
This publication discusses the following topics:
Topic See Page #
Cautions and Warnings 2
Remote Annunciator Installation 3
Power Requirements (4100-9610 and 4100-9611)
Input Voltage 19-33 VDC
Input Current 87 mA standby or alarm
Power Requirements (all models with Flexible User Interface)
Input Voltage 24 VDC
Input Current 186 mA standby, 214 mA alarm
Environmental Specifications
Operating Temperature
32° to 120° F (0° to 49° C)
Humidity
Up to 93% relative humidity at 90° F (32° C)
Introduction
Inspecting Contents
of Shipment
In this Publication
Specifications

Other manuals for Simplex 4100U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100U and is the answer not in the manual?

Simplex 4100U Specifications

General IconGeneral
Control Panel TypeAddressable Fire Alarm Control Panel
DisplayLCD
Power Supply120/240 VAC, 50/60 Hz
Max Signaling Line Circuits (SLC)2
Operating Temperature0°C to 49°C (32°F to 120°F)
Humidity Range10% to 93% non-condensing
Network CapabilityYes
Communication ProtocolRS-232, RS-485
Battery Backup24 VDC
NAC Outputs4
Signaling Line Circuits (SLCs)2
Power Supply Current3.0 A
Max Notification Appliance Circuits (NAC)4
Max Releasing Circuits4
Max Relay Circuits4
Communication PortsRS-232, RS-485