Features
4100U Series MINIPLEX transponders allow
remotely located initiating and notification
functions:
• Transponder operation is available as standard or with
local mode operation
• Communications with the host fire alarm control panel
use the Remote Unit Interface (RUI) format
Initiating functions include:
• Conventional initiating device circuit (IDC) support
• Addressable device support including TrueAlarm
®
analog sensor compatibility
Notification functions include:
• Conventional DC notification appliance circuits
• Emergency voice/alarm communications
• TrueAlert™ addressable strobe and horn notification
Local mode operation provides:
• Default local initiating and notification operation in the
event of a communications loss with the host control panel
• Enabling of an optional Local Mode Controller with a
local alarm sounder, LED status indicators, and
keyswitch enabled control switches
• Support for IDNet addressable devices, conventional
and TrueAlert™ addressable notification appliances,
and default output tones from local amplifiers
Optional modules include:
• Digital or Analog audio riser modules for connection to
system audio signals
• Digital or analog input audio amplifiers with integral
on-board NACs
• Power supplies with or without battery chargers
• City Connect modules and RS-232 ports for printers or
maintenance terminals
• Alarm relays, auxiliary relays, additional IDC modules,
and NAC expansion modules
Cabinets are equipped with solid doors and are
available in beige or red and in two or three bay sizes
Listed to:
• UL Std. 864, Fire Detection and Control (UOJZ), and
Smoke Control Service (UUKL)
• UL Std. 2017, Process Management Equipment (QVAX)
• UL Std. 1076, Proprietary Alarm Units-Burglar (APOU)
• UL Std. 1730, Smoke Detector Monitor (UULH)
• ULC Std. S527-99
* See page 4 for product that is listed as UL or ULC. This product has been approved by the
California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health
and Safety Code. See CSFM Listing 7165-0026:251 (non-high rise) and 7170-0026:250
(high rise) for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Additional
listings may be applicable; contact your local Simplex® product supplier for the latest
status.
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
On
Off
Auto
Press ACK locat ed und er fl a shi ng in di cat or .
Repea t op erat io n unt i l all ev ents ar e ackno wledged.
Local tone will s ilenc e.
A B C
AC Power
D E F G H I
J K L M N OP Q R
'SP' ( ), 0 :
S T U V W XY Z /
ALARMS
Fire Al arm Priorit y 2 Al ar m
SYSTEM WARNINGS
Supervisory Trouble
Alarm Silenced
Emergency Operating Instructions
Alarm or Warning Condition
How to Acknowledge / View Events
How to Silence Building Signals
System ind icato r fl ashi ng . T one On . Press
Alarm Silence.
How t o R es e t Syst em
Press
System Reset.
Press
Ack
to silence tone de vice.
ZONE
1
SIG
2
AUX
3
FB
4
IO
5
IDNet
6
P
7
A
8
L
9
NET AD DR
0
DEL
Enter C/Ex it
Fire Alarm
Ack
Priority 2
Ack
Supv
Ack
Troubl e
Ack
Alarm
Silence
System
Reset
Event
Time
Enable
On
Arm
Disable
Off
Disarm
Auto
Lamp
Test
More
Info
Menu
Previo us
Next
SYSTEM IS NORMAL
08:23:43 am MON 11-DEC-00
Fire Control
4100U Fire Alarm Control Panel
with Voice Control
ALARMFIRE
PULL DOWN
C
A
U
T
I
O
N
C
A
U
T
I
O
N
DISCONNECT
A.C. POWER
AND
BATTERY
BEFORE
SERVICING
DISCONNECT
A.C. POWER
AND
BATTERY
BEFORE
SERVICING
Addressable devices
Audio NAC
Fire Ala rm Local Mode Contr oller
ENABLE
CONTROL
Alarm
Alarm
Silenced
Local
Mode
Active
Power
On
Alarm
Silence
Reset
Local
Mode
Control
Local mode
controller
Strobe NAC
MINIPLEX transponder
Typical 4100U MINIPLEX System One-Line Drawing
Introduction
4100U MINIPLEX transponders connect to a host
4100U Fire Alarm Control Panel using Simplex remote
unit interface (RUI) communications. At the transponder,
RUI communications are received by the transponder
interface module and translated into the same internal
communications format that is used in the host control
panel.
Remotely located modules. With RUI
communications, the transponder can remotely provide
the same initiating and notification functions that occur at
the host control panel without requiring multiple long
distance wiring runs. Connections to the host panel are
low current communications and audio wiring with
distances up to 2500 ft (762 m).
(Please refer to document S4100-0031 and the other
documents listed on page 6 for additional information
concerning the extensive initiating and notification
features of the 4100U fire alarm control panels.)
** Simplex TrueAlarm analog smoke detection, and IDNet and MAPNET II addressable
devices are protected by one or more of the following U.S. Patents: 5,155,468;
5,173,683; 5,543,777; 5,400,014; 5,552,765; 5,552,763; DES. 377,460.
Fire Control Panels
UL, ULC Listed; FM, CSFM, Addressable Fire Detection and Control
and MEA (NYC) Approved* MINIPLEX
®
Transponders
S4100-0035-2 5/02