SERVICE INSTRUCTIONS 
TYPE 4208 FIRE  ALARM  SYSTEMS 
‘1’Y l’r.  --A” 
s’l  Al‘lUN  YANEL 
INTRODUCTION 
The  “A”  panel is the control  center of the 4208 
battery  power  during  an AC power failure  without 
DC system.  It  contains two  independent zone cir- 
interfering  with  the  normal  operation  of  the  trou-  : 
cuits and each zone has its own  trouble  and alarm 
ble and alarm circuits. 
circuits. 
The  “A”  panel  will  transfer  to  stand-by 
CIRCUIT  OPERATION  (FIG.  1) 
POWER SUPPLY 
Normal Operation 
During  normal  operation,  12OVAC  is  trans- 
formed  and  rectified  to  24VDC.  This  24VDC  is 
applied  to  the  NORMAL  POWER  lamp  (illumi- 
nating  the  lamp)  and  also to  relay Kl  (energizing 
relay  Kl). 
When relay  Kl  energizes, its  contacts  transfer 
and -24VDC  is applied to  the -24 terminals  in  the 
system. 
Note:  The  +24VDC  in  the  circuit  description 
and  in  the wiring  diagrams is the  system “com- 
mon.”  The  potential  at  points  labeled  +24  is 
actually  the  “0”  reference  with  respect  to 
-24VDC.  The  difference  in  potential  between 
points labeled +24 and -24 is 24V not  48V. 
Power Failure  Condition 
If  a power  failure  occurs, relay Kl  de-energizes 
and the  NORMAL  POWER lamp goes out.  When 
the  Kl  contacts  transfer,  stand-by  battery  power 
(-24VDC)  is applied  to  terminals  -24VDC  and  to 
terminal  5. 
Standby  battery  power  is applied  to  terminals 
-24VDC  to  insure normal  operation  of  the  system 
trouble  and alarm circuits.  Current  flows  from  ter- 
minal  -BAT.  through  contacts KlA  (4&l)  to termi- 
nals -24VDC. 
The  battery  also applies -24VDC  to  terminal  5 
to indicate a trouble  condition.  Current  flows from 
terminal -BAT,  through  contacts KlA  (4&l  ), diode 
D9,  contacts  KIB  (8&5)  to  terminal  5.  Refer  to 
“A”  Panel 
-  Trouble  Condition,  paragraph three 
for  detailed circuit  description. 
When power  is restored, relay  Kl  energizes and 
its contacts transfer.  When the KlA  and KlB  con- 
tacts transfer,  -24VDC is removed from  terminal  5, 
the  COMMON  TROUBLE  lamp  goes out  and the 
Sonalert  sounds  (“ring-back”).  Refer  to  “A” 
Panel 
-  Trouble  Repaired  for  detailed  circuit 
description. 
ZONE CIRCUIT 
Normal Operation 
During  normal  operation,  current  from  terminal 
-24VDC splits into  two  paths. 
One path  is through  resistor  Rl,  terminal  8, the 
zone ALARM  lamp (dimly  illuminating  the  lamp) 
to  terminal  +BAT.  Resistor  Rl  limits  the  current 
through  the  ALARM  lamp  so  that  the  filament 
glows dimly.  This permits  visual monitoring  of the 
ALARM  lamp filaments. 
7