579-1203 Installation Instructions
579-1203
Rev. B
Appliance specifications
Environmental specifications
Rated DC control/strobe
voltage range
Special application 23-30 VDC
Temperature range
32 °F to 120 °F (0 °C to 49 °C)
Humidity range
10 % to 93 %, non-condensing at
104 °F (40 °C)
Connections
Terminal for 18 AWG to 12 AWG
(0.82 mm
2
to 3.31 mm
2
)
CAUTION:
The appliances are available in red and white. Do not paint
or otherwise alter the factory finishes in any way.
Maximum RMS operating current
49[SV/HFV] visible 49[SVH/HFVH] visible
Candela
Current
Candela
Current
15
59 mA - -
30
82 mA 110 235 mA
75
145 mA 135 255 mA
110
193 mA 185 295 mA
Speaker Only
SO 9 mA
Vertical and horizontal light dispersion ratings
(ceiling to walls and floors)
Percent of rated light output at any candela setting
(room temperature)
Vertical dispersion Horizontal dispersion
Y-plane
angle
UL req
output
Typical
output
X-plane
angle
UL Req
output
Typical
output
0
100
% 327 %
0
100 % 343 %
±5
90
% 293 %
±5
90 % 160 %
±10
90
% 281 %
±10
90 % 175 %
±15
90
% 197 %
±15
90 % 129 %
±20
90
% 168 %
±20
90 % 145 %
±25
90
% 142 %
±25
90 % 165 %
±30
45
% 143 %
±30
45 % 152 %
±35
45
% 155 %
±35
45 % 144 %
±40
45
% 156 %
±40
45 % 139 %
±45
45
% 134 %
±45
45 % 129 %
±50
55
% 115 %
±50
55 % 129 %
±55
45
% 104 %
±55
45 % 123 %
±60
40
% 103 %
±60
40 % 111 %
±65
35
%98 %
±65
35 % 120 %
±70
35
%87 %
±70
35 % 103 %
±75
30
%90 %
±75
30 %75 %
±80
30
%96 %
±80
30 %83 %
±85
25
%96 %
±85
25 %70 %
±90
25
%83 %
±90
25 %47 %
Speaker specifications
Input voltage 25 VRMS or 70.7 VRMS - speakers are for connection to compatible fire alarm audio circuits.
Power taps via jumper J1 1/4 W, 1/2 W, 1 W and 2 W
Frequency
Response
Fire alarm 400 Hz to 4000 Hz [SV/SO]; 200 Hz to 10000 Hz [HFV/HF]
General signaling 125 Hz to 12 kHz
TrueAlert Addressable Ceiling Mount S/V and SO units- speaker switch setting (25 V or 70 V audio)
-
Tap settings in
Watts
UL1480 at 10 ft ULC-S541 at 3 m
HiSPL (SV/SO)
models
HiFi (HFV/HF)
models
HiSPL (SV/SO)
models
HiFi (HFV/HF)
models
Speaker
Only
1/4 79 77 81 78
1/2 83 81 85 82
186 84 88 85*
290 87 91 88*
Speaker
Visible
1/4 79 76 79 78
1/2 83 80 83 82
186 84 86 85*
289 87 89 88*
Note:
Reverberant dBA measurements are a minimum UL rating based on sound level measurements made in UL’s reverberant test chamber.
Anechoic dBA measurements are a minimum ULC rating based on sound pressure level measurements made in ULC’s anechoic test chamber.
The sound pressure level decreases by 3 dB at an angular displacement of 70° from the line perpendicular to the speaker’s center. The SPL
decreases by 6
dB at an angle of 80° from that line.
Only marked settings may be used for ULC fire alarm applications.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 49SVC-CWFIRE and is the answer not in the manual?

Simplex 49SVC-CWFIRE Specifications

General IconGeneral
BrandSimplex
Model49SVC-CWFIRE
CategoryFire Alarms
LanguageEnglish

Related product manuals