Features
Individually addressed and controlled
multi-candela S/V (speaker/visible) notification
appliances provide:
Multi-candela xenon strobe with synchronized 1 Hz
flash rate and with intensity programmable from the
control panel or jumper selected as 15, 30, 75, or
110 cd
Advanced addressable notification controlled by IDNAC
SLCs from Simplex
®
4100ES fire alarm control panels
with EPS/EPS+ power supplies (and 4009 IDNAC
Repeaters) providing regulated 29 VRMS allowing
strobes to operate with lower current even under battery
backup
Wiring supervision to each strobe allowing “T-tapped”
connections for Class B circuits to simplify wiring
(Class A circuits require in/out wiring)
TrueAlert Device Reports at the control panel detailing
appliance point ID, custom label, type, and candela
setting (see sample on page 2)
Magnet test diagnostics to assist checkout and testing of
appliances and wiring
Compatibility with ADA requirements; (refer to
important installation information on page 3)
Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 4)
Strobe operation is listed to UL 1971 and ULC-S526*
LED indicator and magnet test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the
intensity selection; a brief output of the strobe is also
selectable to confirm operation
Mechanical design features:
Rugged, high impact, flame retardant thermoplastic
housings are available for wall or ceiling mount
Wall mount housings are available in red or white
Wall mount options include electrical box adapters,
separate covers to convert color, and red wire guards
Ceiling mount housing is white
Audible notification appliance (speaker):
High quality voice and tone reproduction with taps for
¼, ½, 1, or 2 W, at 25 or 70.7 VRMS
Speakers have capacitor input for connection to DC
supervised NACs and are wired separately from strobes
Listed to UL 1480 and ULC S541*
Compliant with NFPA 72, 520 Hz Low Frequency
Signal Requirements for Sleeping Areas
* See page 2 for additional listing details and wire guard listings. This product has been
approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the
California Health and Safety Code. See CSFM Listing 7320-0026:322 for allowable values
and/or conditions concerning material presented in this document.
Accepted for use – City
of New York Department of Buildings – MEA35-93E. Additional listings may be applicable;
contact your local Simplex product supplier for the latest status. Listings and approvals
under Simplex Time Recorder Co. are the property of Tyco Fire Protection Products.
Wall and Ceiling Mount S/Vs with Addressable Strobes
Description
Multi-Candela TrueAlert S/Vs with speaker and
addressable strobe provide convenient installation to
standard electrical boxes with extensions. The strobe is
individually addressed and individually controlled with
power, supervision, and control supplied from a Simplex
fire alarm control panel providing IDNAC Signaling Line
Circuits (SLCs). (See compatibility list on page 4.)
Speakers are wired separately.
Strobe Application Reference
Proper selection of visible notification is dependent on
occupancy, location, local codes, and proper applications
of: the National Fire Alarm and Signaling Code
(NFPA 72), ANSI A117.1; the appropriate model
building code: BOCA, ICBO, or SBCCI; and the
application guidelines of the Americans with Disabilities
Act (ADA).
IDNAC SLC Operation Advantage
TrueAlert S/V Appliances with Addressable
Strobes on IDNAC SLCs provide visible notification
using a single two-wire circuit that also confirms
connection to the individual notification appliance’s
electronic circuit. This operation increases circuit
supervision integrity by providing supervision that
extends beyond the appliance wiring connections.
TrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved; Multi-Candela Speaker/Visible
MEA (NYC) Acceptance* (S/V) Appliances
S4906-0006-7 5/2014
Question and Answer IconNeed help?

Do you have a question about the Simplex 4906-9253 and is the answer not in the manual?

Simplex 4906-9253 Specifications

General IconGeneral
BrandSimplex
Model4906-9253
CategoryFire Alarms
LanguageEnglish

Summary

Features

LED Indicator and Magnet Test Feature

Details the appliance LED functionality for supervision and the magnet test for diagnostics and operation verification.

Mechanical Design Features

Describes the rugged construction, high impact thermoplastic housings, and available mounting options for wall and ceiling.

Audible Notification Appliance (Speaker)

Covers speaker quality, power taps, input for DC supervised NACs, and compliance with NFPA 72 low frequency requirements.

Product Description and Operation

Description

Provides an overview of the multi-candela TrueAlert S/Vs, highlighting their individual addressing and control via IDNAC SLCs.

Strobe Application Reference

Guides the selection of visible notification based on occupancy, location, local codes, and ADA application guidelines.

IDNAC SLC Operation Advantage

Explains the benefits of using IDNAC SLCs for appliance operation, including reduced current and improved supervision integrity.

Installation and Diagnostics

Reducing Installation and Testing Time

Details how T-tapping wiring and magnet test features significantly reduce installation time and cost.

TrueAlert Addressable Wiring Isolator

Describes the 4905-9929 wiring isolator for remote mounting to isolate short-circuited wiring on TrueAlert circuits.

TrueAlert Addressable Diagnostics

Covers diagnostic features like LED pulsing for address indication and strobe flashing for operational confirmation.

Installation References and Specifications

Wall Mount Installation Reference

Provides detailed instructions and diagrams for wall mount installations using various electrical boxes and adapters.

Ceiling Mount S;V Install Reference and Tile Bridge Dimensions

Details ceiling mount installation requirements and provides dimensions for the 2905-9946 Tile Bridge.

Compatibility and Ratings

TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference

Lists compatible controllers, their data sheets, and the IDNAC SLC output voltage and appliance voltage reference.

TrueAlert Strobe LEGACY Compatibility Reference

Outlines compatibility with legacy systems, listing controllers, output, and available strobe intensity and minimum voltage.

Electrical Ratings Difference for Retrofit Applications

Details current ratings for 17 VRMS applications when connected to TrueAlert addressable SLCs for wall and ceiling appliances.