4903 TrueAlert
Ceiling-Mount A/V
Installation Instructions
2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice.
TrueAlert is a trademark of Simplex Time Recorder Company.
Suffix “C” or “CA” following an eight-digit product ID number denotes ULC-listed product.
574-929
Rev. B
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking your Simplex product, inspect
the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs.
Servicing should be performed by qualified Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Therefore, handle as follows:
1. Ground yourself before opening or installing components.
2. Keep uninstalled component wrapped in anti-static material at all times (use the 553-484 Static Control Kit).
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can radiate radio frequency energy and
if not installed and used in accordance with the instruction manual, may cause interference to radio
communications. It has been tested and found to comply with the limits for a Class A computing device pursuant
to Subpart J of Part 15 of FCC Rules, which are designed to provide reasonable protection against such
interference when operated in a commercial environment. Operation of this equipment in a residential area may
cause interference in which case the user, at his own expense, will be required to take whatever measures may be
required to correct the interference.
TrueAlert
Ceiling-Mount A/V Operation
The 4903 TrueAlert Audible/Visible (A/V) unit (see Figure 1) is a
ceiling-mount notification appliance that provides an audible and/or visible
warning indication of an alarm condition when activated from a TrueAlert-
compatible control panel of a UL-listed Simplex Fire Alarm System. When the
notification appliance emits sound and/or light, it indicates the possibility of
an emergency situation that requires your immediate attention.
The TrueAlert A/V unit is a notification appliance that operates only on a
TrueAlert-compatible Signaling Line Circuit (SLC). The appliance is
supervised via communications with the TrueAlert Addressable Controller
(rather than via conventional appliance supervision).
The Ceiling-Mount TrueAlert A/V unit responds to communication signals over the circuit from a TrueAlert-compatible
panel. Coded messages from the TrueAlert Addressable Controller turn on the A/V strobe and horn. The Strobe can
only be operated through a 4009-9401 TrueAlert Addressable Controller using Simplex TrueAlert Comm Channel
communications. The appliance is supervised via communications with the TrueAlert controller (rather than via
conventional current flow supervision).
The A/V horn provides selectable high/low volume sound pressure levels with audible output types of Steady, Temporal, and
March Time (fast/slow). The compatible 4009 TrueAlert Addressable Controller or FACP is used to configure the features.
Note: The TrueAlert Ceiling-Mount A/V will not operate on a conventional NAC.
TrueAlert ceiling-mount A/Vs are available rated at 15 candela, 75 candela, and 110 candela. Table 1 lists the available
ceiling-mount A/V models.
Table 1. Ceiling-Mount TrueAlert A/V Models
Description Model Cover Color
Ceiling-Mount A/V 15 CANDELA 4903-9459
Ceiling-Mount A/V 75 CANDELA 4903-9460
Ceiling-Mount A/V 110 CANDELA 4903-9461
White
Figure 1. TrueAlert Ceiling-Mount A/V
firealarmresources.com
Question and Answer IconNeed help?

Do you have a question about the Simplex TrueAlert 4903 and is the answer not in the manual?

Simplex TrueAlert 4903 Specifications

General IconGeneral
CategoryFire Alarms
ManufacturerSimplex
ModelTrueAlert 4903
Voltage24 VDC
ColorWhite
Candela Ratings15, 30, 75, 110
Operating Temperature0°C to 49°C
Humidity Range10% to 93% non-condensing
Dimensions5.5 in x 5.5 in x 2.5 in
Weight1.5 lbs
MaterialPlastic
CompatibilitySimplex fire alarm control panels
Strobe TypeXenon

Summary

Cautions and Warnings

Hazard and Compliance Warnings

Covers electrical, static, and RF energy hazards and compliance requirements.

TrueAlert Ceiling-Mount A/V Operation

Explains the function, communication, supervision, and audible features of the A/V unit.

Available Models

Lists the available ceiling-mount A/V models with their candela ratings.

TrueAlert Ceiling-Mount A/V Wiring

Wiring Precautions and Diagrams

Details wiring connections, precautions, Class A/B diagrams, and SLC limitations.

Mounting the TrueAlert Ceiling-Mount A/V

Mounting Instructions and Precautions

Covers mounting to electrical boxes, screw torque, and installation considerations.

Setting the Ceiling-Mount A/V Address

DIP Switch Configuration

Instructions on setting the appliance address using DIP switches.

Magnetic Test Procedure

Guide to performing a magnetic test for address verification and alarm function.

Current and Sound Pressure Measurements

Electrical and Acoustic Performance Data

Presents charts for current ratings and sound pressure levels at various settings.

Limitations, Safety and Placement

Product Limitations and System Requirements

Details operational limitations, power requirements, and output level considerations.

Installation Safety and Placement Guidelines

Emphasizes safety precautions, electrical hazards, and adherence to placement standards.