Simplex 4906-9253 - Compatibility and Ratings; TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference; TrueAlert Strobe LEGACY Compatibility Reference; Electrical Ratings Difference for Retrofit Applications

Simplex 4906-9253
4 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA S4906-0006-7 5/2014
www.simplex-fire.com
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Common Specifications (see page 2 for appliance dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections
Terminal blocks for 18 AWG to 12 AWG (0.82 mm
2
to 3.31 mm
2
); two wires per terminal
for in/out wiring
Installation Instructions 579-808
Speaker General Specifications
Input Voltage 25 or 70.7 VRMS, see Note 1 below
Power Taps ¼, ½, 1, and 2 W
Frequency Response
Fire Alarm 400 to 4000 Hz
General Signaling 125 to 12 kHz
Speaker Output Ratings @ 10 ft (3 m) (see Note below)
Wattage Tap ¼ W ½ W 1 W 2 W
UL Listed Models, Reverberant Chamber Test, per UL 1480 76 dBA 79 dBA 82 dBA 85 dBA
Wall Mount Models 4906-9251 and 4906-9253, Anechoic
Chamber Test, per ULC-S541
77 dBA 80 dBA 83 dBA 86 dBA*
Ceiling Mount Model 4906-9257, Anechoic
Chamber Test per ULC-S541
25 VRMS Input 81.6 dBA 84.3 dBA 87.1 dBA* 89.7 dBA*
70.7 VRMS Input 80.9 dBA 84.1 dBA 87.3 dBA* 90.2 dBA*
* NOTE: Select taps as indicated to satisfy the ULC fire alarm applications requirement of 85 dBA minimum
Polar Dispersion Reference (per ULC-S541 Anechoic Chamber
Testing)
Attenuation Angle Attenuation Angle
-3 dB +/- 30° off-axis -6 dB +/- 55° off-axis
Strobe Specifications
Typical Operating Voltage Range
23 VRMS to 31 VRMS, Special Application (see below for 17 VRMS
rating)
Flash Rate and Synchronized SLC Loading
1 Hz; with up to 46 synchronized strobes maximum per NAC; maximum
30 resistance between appliances
Wall Mount
Appliances
Candela Setting
15 cd 30 cd 75 cd 110 cd
23 VRMS Current Ratings, for connection to
IDNAC Addressable SLCs
50 mA 75 mA 137 mA 190 mA
Ceiling Mount
Appliances
23 VRMS Current Ratings, for connection to
IDNAC Addressable SLCs
60 mA 92 mA 180 mA 240 mA
Note: Speakers are for connection to conventional fire alarm audio circuits. Anechoic speaker output ratings are typically more
representative of actual installed sound output.
Compatible Controller
Data Sheet
Reference
Controller Output
Available Strobe
Intensity
Appliance Voltage
Minimum
4100ES or 4100U with TrueAlert Power Supply S4100-0031
TrueAlert
Addressable SLC
15, 30, 75, and
110 cd
17
VRMS 4009 TPS, Remote TrueAlert Power Supply S4100-0037
TrueAlert Addressable Controller (4009T) S4009-0003
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VRMS to 31 VRMS, Special Application
Candela Setting 15 cd 30 cd 75 cd 110 cd
17 VRMS Current Ratings, use
when connected to TrueAlert
Addressable SLCs per above
Wall
Mount
Appliances
64 mA 98 mA 187 mA 253 mA
Ceiling Mount
Appliances
76 mA 128 mA 242 mA 328 mA
Compatible Controller
Data Sheet
Reference
Controller Output
IDNAC SLC
Output Voltage
Appliance Voltage
Design Reference
4100ES with EPS+ or EPS Power Supply S4100-0100
IDNAC SLC
29 VRMS
(regulated)
23 VRMS
(with 6 VRMS drop)
4009 IDNAC Repeater S4009-0004
S/V Specifications
TrueAlert Strobe LEGACY Compatibility Reference
TrueAlert Strobe and IDNAC SLC Controller Compatibility Reference