14
fuel level. If a High Level Alarm condition occurs
and the Day Tank fuel level is reduced to normal
levels the High Level L.E.D. will remain illuminated
until it is reset by the operator. e operator must
place the Day Tank mode selector switch in the O
position and then return it to the Manual or Auto-
matic position to reset the High Level failure. When
High Level is initiated while in Automatic Mode
the Day Tank will continue to operate normally and
cycle from 50% to 90% but the High Level L.E.D. will
remain illuminated until it is reset. When the High
Level mode is initiated while in Manual Mode the
Day Tank pump/motor will cycle between the 90%
and 95% levels as determined by fuel level sensors
FS3 and FS4. Aer the condition is corrected and the
control circuitry is returned to Auto the pump/motor
will resume normal operation and cycle between 50%
and 90%.Fuel level sensors FS1-FS3 (Low Fuel Level
Alarm, Fill Start, and Tank Full, respectively) have
normally closed contacts. FS4 (High Level Alarm)
is the only fuel level sensor with normally open
contacts.
e Fill Test pushbutton is a momentary type. It
may be used to provide a quick verication of overall
pump/motor/fuel level sensor operation when the
system is in the Auto mode. When the mode selec-
tor switch is placed in the O position, the Fill Test
pushbutton is disabled. When the mode selector
switch is in the Automatic position, the Fill Test
pushbutton is enabled.
e operator may energize the pump/motor with
the Test Fill pushbutton to test and cycle the Day
Tank through the specied capacity range. When the
pump is operated by continuously holding the Fill
Test pushbutton the pump/motor will continue to
run past the normal stop level until 95% capacity is
reached, at which point the pump/motor is de-en-
ergized and locked out by fuel level sensor FS4. e
High Level L.E.D. will be illuminated and the High
Level alarm relay will be energized. Contact rated 5A
@ 30 VDC, 5A @ 125VAC maximum.
During normal operation, the pump/motor is ener-
gized and the Fill Start L.E.D. is illuminated when
the Day Tank fuel level reaches 50% capacity. If the
fIll teSt
puSHbutton
low level fIll
alarm