IMPORTANT: When the notification appliance emits light or sound, it indicates the possibility of an emergency situation that
requires the immediate attention of all occupants.
LOCATION REFERENCE: Location and quantity of appliances required must conform to the applicable local standards and
guidelines (the National Fire Alarm and Signaling Code (NFPA 72); ULC Standard CAN/ULC-S524, Installation of Fire Alarm
Systems; the appropriate model building codes, etc.) and specific requirements of the Local Authority Having Jurisdiction (AHJ).
These notification appliances are not intended for installation within hazardous locations as defined by the National Electrical
Code (NEC) or NFPA.
SAFETY: Always install, maintain, and test notification appliances within their specifications. Failure to follow all safety
precautions and instructions may result in loss of life and property due to non-functioning notification appliances. Some
notification appliances use high voltage. To avoid electrical hazards and avoid damage to appliances, make sure that the
electrical power for the notification appliance circuit is disconnected at the control panel before installing, repairing, or internally
adjusting any notification appliances. Even with electrical power removed, some notification appliances (such as visible strobes)
store a high voltage charge. The high voltage can cause injury resulting in death from electrical shock. DO NOT TOUCH
EXPOSED CIRCUITRY.
Mounting instructions
1. Select the mounting location and install the electrical box using screws suitable for the mounting surface. See Figure 1 for mounting
and location information.
2. Bring the building wiring through the rectangular opening in the backplate.
3. Connect the building wires to the backplate. See the wiring section on page 2.
4. Secure the backplate to the electrical box using the provided hardware. Install with the writing Install this side up at the top. Use a
torque wrench to tighten the screws to 12-15 inch-pounds. Do not over-tighten the screws.
5. Attach the cover to the appliance.
6. Set the appliance settings. See page 3.
7. Attach the assembled appliance onto the backplate.
UL listed TrueAlert ES indoor product identification reference
Type Colors Models Operation
Wall Mount Horn
Audible Only (AO)
• Red
• White
Complete
appliances:
49AO-WRF
49AO-WRF-BA
49AO-WRS-BA
49AO-WWF
49AO-WWF-BA
49AO-WWS-BA
49AO-WRS
49AO-WRQ
Components:
49AO-APPLW
49AO-APPLW-BA
Backplate:
49MP-AVVOWR
49MP-AVVOWW
Covers:
49AOC-WRBLNG
49AOC-WRFEU
49AOC-WRFIRE
49AOC-WRS
49AOC-RBLANK
49AOC-WWBLNG
49AOC-WWFEU
49AOC-WWFIRE
49AOC-WWS
49AOC-WBLANK
These appliances provide an audible (AO) warning of an alarm
condition when activated from the control panel of a compatible
UL/ULC Listed, Simplex Fire Alarm System.
Note: For information about TrueAlert ES appliance testing, see TrueAlert ES Addressable Appliances testing and applications guide (579-1049).
Kit contents Appliance x 1 Cover x 1 Backplate x1 with 8-32 1 inch mounting screws x 2, and 6-32 1 inch mounting screws x 2.
Not included Electrical box 1-1/2 inch (38.1 mm) minimum depth required: single gang, double gang, or 4 inch (101.6 mm) square.
Figure 1. Mounting instructions
NFPA 72 requires that
the device is not
less than 80 in. (203.2 cm)
and not greater than
96 in. (243.8 cm) above
the finished floor.
Single gang, double gang, or
4 in. (101.6 mm) square electrical box
Backplate
Appliance cover
Building wire
Screws: Use 8-32 screws for a 4 in. (101.6 mm) square electrical box
Use 6-32 screws for a single or a double gang electrical box
Appliance
TrueAlert ES Addressable
Indoor A/O Notification Appliances
Installation Instructions
Question and Answer IconNeed help?

Do you have a question about the Simplex TrueAlert ES Series and is the answer not in the manual?

Simplex TrueAlert ES Series Specifications

General IconGeneral
BrandSimplex
ModelTrueAlert ES Series
CategoryIntercom System
LanguageEnglish

Summary

Mounting Instructions

Kit Contents and Requirements

Lists included installation hardware and required electrical boxes for mounting the appliance.

Installation Steps

Details connecting wiring, securing the backplate, and attaching the appliance cover during installation.

Wiring Instructions

Connection Procedure

Guides connecting building wiring to terminals and ensuring proper continuity and polarity.

Wiring Notes and Limitations

Covers circuit capacity, wire resistance, polarity, voltage limits, and T-tapping restrictions.

Setting the Address DIP Switch

Address Setting Procedure

Steps to unclip the appliance, set the DIP switches using a non-metallic tool, and record the address.

Setting the Horn Configuration Switch

AO Settings Configuration

Describes how to configure horn volume, CAN Horn mode, and Legacy NAC mode using DIP switches.

Appliance Specifications

Environmental Specifications

Details the rated voltage range, operating temperature, humidity, and connection types for the appliance.

Sound Pressure Level (dBA)

Presents dBA measurements for horn output at different volume settings and distances.

Current Draw

Specifies the maximum RMS operating current for the appliance.

ULC Directional Characteristics