579-1032 Rev F
© 2017 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. Additional listings may be applicable, contact your local Simplex® product supplier for
the latest status. Listings and approvals under Simplex Time Recorder Co. Simplex, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm Code are registered
trademarks of the National Fire Protection Association (NFPA).
Table 4: Current draw
Application Candela selection Appliance type Maximum RMS operating current
VO 212 mA
WP75
A/V 238 mA
VO 239 mA
UL1638, to -35
o
C
WP185
A/V 274 mA
VO 160 mA
WP75
A/V 163 mA
VO 185 mA
UL1638, to 0
o
C
WP185
A/V 189 mA
VO 60 mA
15
A/V 80 mA
VO 160 mA
UL1971 (0 TO 49
o
C)
75
A/V 165 mA
Table 5: Percent of rated light output at any candela setting (room temperature) (15cd and 75 cd only)
Vertical dispersion Horizontal dispersion
Y-plane angle UL Req output Typical output X-Plane angle UL Req output Typical output
0 100% 249% 0 100% 249%
5 90% 168% ±5 90% 176%
10 90% 145% ±10 90% 157%
15 90% 164% ±15 90% 167%
20 90% 160% ±20 90% 165%
25 90% 138% ±25 90% 152%
30 90% 143% ±30 75% 167%
35 65% 180% ±35 75% 167%
40 46% 165% ±40 75% 148%
45 34% 147% ±45 75% 129%
50 27% 150% ±50 55% 117%
55 22% 141% ±55 45% 113%
60 18% 147% ±60 40% 112%
65 16% 137% ±65 35% 99%
70 15% 133% ±70 35% 95%
75 13% 105% ±75 30% 91%
80 12% 85% ±80 30% 89%
85 12% 61% ±85 25% 80%
90 12% 36% ±90 25% 60%