around the equipment is to be surveyed to make sure that there are no 
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.   
6) Ventilated area   
Ensure that the area is in the open or that it is adequately ventilated before 
breaking into the system or conducting any hot work. A degree of ventilation shall 
continue during the period that the work is carried out. The ventilation should 
safely disperse any released refrigerant and preferably expel it externally into the 
atmosphere.   
7) Checks to the refrigeration equipment   
Where electrical components are being changed, they shall be fit for the purpose 
and to the correct specification. At all times the manufacturer’s maintenance and 
service guidelines shall be followed. If in doubt consult the manufacturer’s 
technical department for assistance.     
The following checks shall be applied to installations using flammable 
refrigerants:     
– The charge size is in accordance with the room size within which the refrigerant   
containing parts are installed;     
– The ventilation machinery and outlets are operating adequately and are not 
obstructed; 
– If an indirect refrigerating circuit is being used, the secondary circuit shall be 
checked for the presence of refrigerant;     
– Marking to the equipment continues to be visible and legible. Markings and 
signs that are illegible shall be corrected;     
– Refrigeration pipe or components are installed in a position where they are 
unlikely to be exposed to any substance which may corrode refrigerant 
containing components, unless the components are constructed of materials 
which are inherently resistant to being corroded or are suitably protected 
against being so corroded.