Table 7.2: High Static Pressure Duct heating capacity (continued)
Capacity
(kW)
Outdoor air
temperature (°C )
Indoor air temperature (°C DB)
16
18
20
21
22
24
TC
TC
TC
TC
TC
TC
WB
DB
kW
kW
kW
kW
kW
kW
28.0
-20
-19.8
17.64
17.64
17.64
17.64
17.64
17.64
-19
-18.8
18.90
18.90
18.90
18.90
18.90
18.90
-17
-16.7
19.85
19.85
19.85
19.85
19.85
19.85
-15
-14.7
20.48
20.48
20.48
20.48
20.48
20.48
-13.00
-12.60
21.74
21.74
21.74
21.74
21.74
21.74
-11.00
-10.50
22.05
22.37
22.37
22.37
22.37
22.37
-10.00
-9.50
23.00
23.00
23.00
23.00
23.00
23.00
-9.10
-8.50
23.63
23.63
23.63
23.63
23.63
23.63
-7.60
-7.00
23.94
23.94
23.94
23.94
23.94
23.94
-5.60
-5.00
24.89
24.89
24.89
24.89
24.89
24.89
-3.70
-3.00
26.15
26.15
26.15
26.15
26.15
26.15
-0.70
0.00
28.04 28.04
28.04
28.04
28.04
26.46
2.20
3.00
29.61 29.61
29.61
29.61
28.98
26.46
4.10
5.00
30.56 30.56
30.56
30.56
28.98
26.46
6.00
7.00
31.50 31.50
31.50
30.56
28.98
26.46
7.90
9.00
32.45 32.45
31.50
30.56
28.98
26.46
9.80
11.00
33.39 33.39
31.50
30.56
28.98
26.46
11.80
13.00
34.65 34.02
31.50
30.56
28.98
26.46
13.70
15.00
35.60 34.02
31.50
30.56
28.98
26.46
Abbreviations:
TC: Total capacity
Notes:
1. Shaded cells indicate rating condition.