User Manual of A90 Series Inverter
94
F09.17
Lower limit of PID
output
–100.0 - F09.16
%
0.0
●
F09.18
PID deviation limit
0.00-100.00 (0.00: invalid)
%
0.00
●
F09.19
PID differential limit
0.00-100.00
%
5.00
●
F09.20
PID integral
separation threshold
0.00-100.00 (100.00% = invalid
integral separation)
%
100.00
●
F09.21
PID setting change
time
0.000-30.000
s
0.000
●
F09.22
PID feedback
filtering time
0.000-30.000
s
0.000
●
F09.23
PID output filtering
time
0.000-30.000
s
0.000
●
F09.24
Upper limit detection
value of PID
feedback
disconnection
0.00-100.00; 100.00 = invalid
feedback disconnection
%
100.00
●
F09.25
Lower limit detection
value of PID
feedback
disconnection
0.00-100.00; 0.00 = invalid
feedback disconnection
%
0.00
●
F09.26
Detection time of PID
feedback
disconnection
0.000-30.000
s
0.000
●
F09.27
PID sleep control
options
0: Invalid
1: sleep at zero speed
2: sleep at lower frequency limit
3: sleep with tube sealed
0
●
F09.29
Sleep delay time
0.0 - 6500.0
s
0.0
●
F09.30
Wake-up action point
0.00-100.00 (100.00 corresponds
to the PID setting feedback range)
%
0.00
●
F09.31
Wake-up delay time
0.0~6,500.0
s
0.0
●
F09.32
Multi-segment PID
setting 1
0.0 to PID setting feedback range
F09.03
0.0
●
F09.33
Multi-segment PID
setting 2
0.0 to PID setting feedback range
F09.03
0.0
●
F09.34
Multi-segment PID
setting 3
0.0 to PID setting feedback range
F09.03
0.0
●
F09.40
Coefficient of
wake-up action point
0.0-100.0 (100% corresponds to
PID setting)
%
90.0
●
F09.41
Pipeline network
alarm overpressure
0.0 to pressure sensor range
F09.03
bar
6.0
●
F09.42
Overpressure
0-3,600 (0: invalid)
S
3
●