User Manual of A90 Series Inverter
136
(F01.00) and motor nameplate parameters (F01.01 to F01.08) correctly. Relevant
parameters (F01.09 to F01.13) of the asynchronous motor can be obtained during static
self-learning.
This mode is mainly used when the motor cannot rotate. Static self-learning has poorer
effects than rotary self-learning.
F01.34=2
: the asynchronous motor rotates during parameter self-identification.
Prior to the rotary self-learning of the asynchronous motor, please set the motor type
(F01.00) and motor nameplate parameters (F01.01 to F01.08) correctly. Relevant
parameters (F01.09 to F01.18) of the asynchronous motor can be obtained during rotary
self-learning.
This mode is mainly used when the motor can rotate. However, loads should be
avoided or minimized; otherwise, self-learning will have poor effects.
F01.34=11
: the synchronous motor remains stationary during parameter
self-identification.
Prior to the static self-learning of the synchronous motor, please set the motor type
(F01.00) and motor nameplate parameters (F01.01 to F01.05) correctly. Relevant
parameters (F01.09 to F01.21) of the synchronous motor and current loop parameters
(F06.12 to F06.15) can be obtained during static self-learning.
This mode is mainly used when the motor cannot rotate. It is necessary to manually
enter the counter electromotive force (F01.22).
F01.34=12
: the synchronous motor rotates during parameter self-identification.
Prior to the rotary self-learning of the synchronous motor, please set the motor type
(F01.00) and motor nameplate parameters (F01.01 to F01.05) correctly. Relevant
parameters (F01.09 to F01.21) of the synchronous motor, current loop parameters (F06.12
to F06.15) and counter electromotive force (F01.22) can be obtained during rotary
self-learning.
This mode is mainly used when the motor can rotate. However, loads should be
avoided or minimized; otherwise, self-learning will have poor effects.
1.
Motor parameter self-learning is valid only in the keyboard-controlled
start/stop mode (F00.02=0): Set F01.34 to the corresponding value, and press
the ENTER key
ENTER
for confirmation and then the RUN key
RUN
to
start motor parameter self-learning. After the parameter self-learning, F01.34