User Manual of A90 Series Inverter
275
information about the latest fault):
Request
Respond
Domain name
(0x)
Domain name (normal)
(0x)
Domain
name
(abnormal)
(0x)
Function code
03
Function code
03
Function
83
Starting address
Hi
13
Number of bytes
0C
Exception
code
03 (example,
the same
below)
Starting address
Lo
00
Register value Hi
(F19.00)
00
Number (Hi) of
registers
00
Register value Lo
(F19.00)
11
Number (Lo) of
registers
06
Register value Hi
(F19.01)
00
Register value Lo
(F19.01)
00
Register value Hi
(F19.02)
00
Register value Lo
(F19.02)
00
Register value Hi
(F19.03)
01
Register value Lo
(F19.03)
2C
Register value Hi
(F19.04)
00
Register value Lo
(F19.04)
00
Register value Hi
(F19.05)
00
Register value Lo
(F19.05)
00
According to the returned data, the “17 (0011H): temperature sensor abnormality”
occurs to the inverter, in which the output frequency is 0.00Hz, the output current is 0.00A,
the bus voltage is 300V (012CH), the acceleration and deceleration status is “standby”, and
the working time is 0 hour.
:
At present, the function code 0x03 of MODBUS protocol supports the reading of