User Manual of A90 Series Inverter
85
stop/no-stop recovery
voltage
F07.11
Current limit control
0: Invalid
1: limit mode 1
2: limit mode 2
2
F07.12
Current limit level
20.0-180.0(100.0 = the rated
current of inverter)
%
150.0
F07.13
Quick current limit
options
0: Invalid
1: valid
0
F07.14
Number of retries
after failure
0-20; 0: disable retry after failure
0
F07.15
Options of digital
output action in
retries after failure
0: no action
1: action
0
F07.16
Interval of retries
after failure
0.01~30.00
s
0.50
F07.17
Restoration time in
retries after failure
0.01~30.00
s
10.00
F07.18
Options of retries
after failure
E07
E03
E02
E06
E05
E0
4
**0
00000
0: allow retry after failure
1: disable retry after failure
F07.19
Action option 1 after
failure
E21
E16
E15
E14
E13
E12
E08
E07
000
00000
0: free stop
1: stop according to stop mode
F07.20
Action option 2 after
failure
E28
E27
E25
E23
*0000
0: free stop
1: stop according to stop mode
F07.21
Options of load loss
protection
0: invalid 1: valid
0
F07.22
Load loss detection
level
0.0~100.0
%
20.0
F07.23
Load loss detection
time
0.0~60.0
s
1.0
F07.24
Options of load loss
protection action
0: free stop
1: stop according to stop mode
1
F07.25
~F07.2
6
Reserved
F07.27
AVR function
0: Invalid
1: valid
2: automatic
1

Table of Contents