EasyManua.ls Logo

SMA SOLID-Q 50 - Page 7

SMA SOLID-Q 50
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA New Energy Technology (Jiangsu) Co., Ltd.
7 SMASOLID-Q-Modbus-TI-en-10 | Version 1.0 Technical Information
4 = Fixed Q value
5 = Q(U) curve
30044
Active Power Mode
0 = None
1 = Fixed Active Power
U16 - - RO
30047
Version of Protocol
-
-
RO
30048
String 1 Current
A
0.1
RO
30049
String 2 Current
A
0.1
RO
30050
String 3 Current
A
0.1
RO
30051
String 4 Current
A
0.1
RO
30052
String 5 Current
A
0.1
RO
30053
String 6 Current
A
0.1
RO
30054
String 7 Current
A
0.1
RO
30055
String 8 Current
A
0.1
RO
30056
String 9 Current
A
0.1
RO
30057
String 10 Current
A
0.1
RO
30058
String 11 Current
A
0.1
RO
30059
String 12 Current
A
0.1
RO
Read and Write Registers
ADR
(DEC)
Description/number code
Type
Unit
Gain
Access
40013
0=Power Off / 1=Power On
-
-
RW
42021
42028
Serial Number (16 digits: 2 ASCII per ADR ..1 to ..8) ASCII - - RW
45001
Grid Code (see Section 4.4)
-
-
RW
45007
Grid Voltage High Limit2
V
0.1
RW
45008
Grid Voltage High Limit Time2
ms
20
RW
45009
Grid Voltage High Limit1
V
0.1
RW
45010
Grid Voltage High Limit Time1
ms
20
RW
45011
Grid Voltage Low Limit2
V
0.1
RW
45012
Grid Voltage Low Limit Time2
ms
20
RW

Related product manuals