26
L
Werkseinstellungen dieses Wechselrichters | Default settings of this inverter | Εργοστασιακές ρυθμίσεις
αυτού του μετατροπέα | Ajustes de fábrica de este inversor | Réglages par défaut de cet onduleur |
Impostazioni di fabbrica di questo inverter | Výrobní nastavení tohoto střídače | Fabrieksinstellingen van
deze omvormer | Nastawy fabryczne falownika | Congurações de fábrica deste inversor
Country Setting: Default
Voltage and frequency monitoring Threshold Max. disconnection time
Lower limit AC voltage
195.5 V 0.2000 s
Upper limit AC voltage
264.5 V 0.2000 s
Lower limit AC frequency
47.50 Hz 0.2000 s
Upper limit AC frequency
51.50 Hz 0.2000 s
Loss of mains active Max. disconnection time
Active islanding detection
No -- s
Time before reconnection active Grid monitoring time
Time to reconnection after a grid failure
No -- s
Grid quality active Threshold
DC injection - max allowed value for the
offset of the AC current
No -- A
Voltage rise protection - monitoring of
10 min. mean value, e.g. as per
EN 50160
Yes 253.0 V
K
Wechselrichter über Ethernet kongurieren | Conguring the inverter via Ethernet | Διαμόρφωση μετατροπέa
μέσω Ethernet | Conguración del inversor mediante ethernet | Conguration de l’onduleur via Ethernet |
Congurazione dell‘inverter mediante Ethernet | Kongurace střídačů prostřednictvím Ethernetu | Omvormers
via ethernet congureren | Konguracja falownika poprzez Ethernet | Congurar inversores via Ethernet
1