Troubleshooting SMA Solar Technology AG
56 SB33_38-IEN111851 Installation Guide
Shutdown Temporary inverter disturbance.
Corrective measures
Contact the SMA Serviceline.
Trafo-Temp-F Temperatures in the transformer have exceeded the acceptable limit.
The inverter stops feeding the grid until the temperature lies within the
acceptable range.
Corrective measures
If this problem recurs, check the heat dissipation of the inverter, as
described in section 8.1”Checking Heat Dissipation” (page47).
Trafo-Temp-W Temperatures in the transformer have exceeded the acceptable limit. The
inverter stops feeding the grid until the temperature lies within the
acceptable range. The Trafo-Temp-W warning is displayed until final
shutdown (at the end of the day).
Corrective measures
Check the heat dissipation of the inverter, as described in section
8.1”Checking Heat Dissipation” (page47).
Vac-Bfr
Vac-Srr
The grid voltage on line 2 is no longer within the permissible range ("Bfr"
or "Srr" is an internal message that has no meaning for the user). This
code can be caused by any of the following conditions:
Grid disconnected (line circuit breaker, fuse),
•AC cable is broken or
AC cable is highly resistive
For safety reasons, the inverter disconnects itself from the grid.
Corrective measures
Check the grid current and grid connection on the inverter.
If the grid voltage lies outside the acceptable range because of
local grid conditions, ask the electric power company if the
voltages can be adjusted at the feed-in point or if they agree to
changes in the values of the monitored operational limits (operating
parameters: Vac-Min and Vac-Max).
If the grid frequency is within the tolerable range, yet "Vac-Bfr", or
"Vac-Srr" faults are still being displayed, please contact the
SMA Serviceline.