Error number Display message, cause and corrective measures
9315
Battery imbalancing fault
The cause must be determined by the SMAServiceLine.
Corrective measures:
Contact the SMAServiceLine.
9334
Battery charging test
The function of the Battery Pack is tested. The Battery Pack is charged.
9335
Discharge battery test
The function of the Battery Pack is tested. The Battery Pack is discharged.
9336
Start conditions for battery test not fulfilled
The function of the Battery Pack cannot be tested because the require-
ments are not fulfilled.
Corrective measures:
Ensure that the requirements for testing the Battery Pack are
fulfilledTesting the Function of the Battery Pack.
9337
Charge battery test successful
The Battery Pack was charged successfully. The function of the Battery
Pack is ensured.
9338
Battery discharging test successful
The Battery Pack was discharged successfully. The function of the Battery
Pack is ensured.
9339
Battery charging test failed
The Battery Pack could not be charged.
Corrective measures:
Ensure that the function of the Battery Pack was tested correctly
Testing the Function of the Battery Pack.
9340
Battery discharging test failed
The Battery Pack could not be discharged.
Corrective measures:
Ensure that the function of the Battery Pack was tested correctly
Testing the Function of the Battery Pack.
4 Troubleshooting
SMA Solar Technology AG
Service Manual 25SB36-50SE-SG-en-10