EasyManua.ls Logo

SMA SUNNY TRIPOWER 12000TL-US - Connecting the Inverter to the Utility Grid

SMA SUNNY TRIPOWER 12000TL-US
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Electrical Connection
SMA Solar Technology America LLC
Installation Manual STPTL-US-10-IA-xx-20 29
Load-break switch and cable protection:
NOTICE
Damage to the inverter due to the use of screw-type fuses as load-break
switch
Screw-type fuses are not load-break switches.
Do not use screw-type fuses as load-break switches.
Use a load-break switch or a circuit breaker for load disconnection.
In PV systems with multiple inverters, protect each inverter with a separate three-phase circuit
breaker. Observe the maximum permissible fuse protection (see Section14 "Technical Data",
page71). This will prevent residual voltage from being present at the corresponding cable
after disconnection.
The load-break switch or circuit breaker must be listed (seeNational Electrical Code
®
, ANSI/
NFPA 70)
Loads installed between the inverter and the circuit breaker must be fused separately.
The overcurrent protection for the AC output circuit is to be provided by others.
Compatible grid configurations:
Device 480V / 277V WYE 480VDelta
STP 12000TL-US-10 Yes No
STP 15000TL-US-10 Yes No
STP 20000TL-US-10 Yes No
STP 24000TL-US-10 Yes No
STP 30000TL-US-10* Yes Yes**
* A neutral conductor connection is necessary for the 480V / 277V WYE. A neutral conductor
connection is not necessary for the 480V Delta.
** For connection to 480 V Delta commercial services where co-located loads may result in recurring and
persistent line-to-ground faults (effectively resulting in a corner grounded Delta grid configuration),
inverters must be protected from excessive line-to-ground voltages by isolating the PV system from the
source(s) of the fault(s).
6.3.2 Connecting the Inverter to the Utility Grid
Requirements:
All electrical installations must be carried out in accordance with the local standards and the
National Electrical Code
®
ANSI/NFPA 70 or the Canadian Electrical Code
®
CSA C22.1.
The AC and DC electric circuits are isolated from the enclosure. If required by the National
Electrical Code
®
, ANSI/NFPA 70, the installer is responsible for grounding the system.
The connection requirements of the grid operator must be met.
The grid voltage must be within the permissible range. The exact operating range of the
inverter is specified in the operating parameters.
ENGLISH

Table of Contents

Related product manuals