What does it mean when my SMA WINDY BOY 3300 Inverter shows 'Vac-Bfr' or 'Vac-Srr'?
- LlindahermanAug 26, 2025
If your SMA Inverter displays 'Vac-Bfr' or 'Vac-Srr', the grid voltage is no longer within the permissible range. Check the grid current and grid connection on the inverter. If the grid voltage is outside the acceptable range due to local grid conditions, ask the utility provider if the voltage can be adjusted or if it would agree to changes in the monitored operational limits (Vac-Min and Vac-Max). If the grid voltage is within the tolerable range, yet the errors persist, contact the SMA Serviceline.