Frequency count unit parameters
No.
Parameter
Definition
Item
Content
Default
setting
Parameter
setting range
1
Monitor short
circuit (power)
Generates error
when the short
circuit of the power
supply for the input
device is detected.
Enable
Generates an error.
Unit
Disable
Does not generate an
error.
2
Filter
Sets filtering time
for the frequency
count value.
None
None
Unitl
2AVG
2 value average
4AVG
4 value average
8AVG
8 value average
3
Monitor upper
limit
Generates error
when the
frequency count
value exceeds the
user setting value.
Enable
Generates an error.
Value: 0 to 65535

Value:
65000
1
Channel
Disable
Does not generate an
error.
4
Monitor lower
limit
Generates error
when the
frequency count
value falls below
the user setting
value.
Enable
Generates an error.
Value: 0 to 65535
1
Value:
0
1
Channel
Disable
Does not generate an
error.
5
Cutoff
frequency
The frequency data
is set to zero when
the frequency
count value falls
below the set
value.
Cutoff
frequency value
Value:0 to 10000

20
1
Channel
1: Frequency for setting is set value × 0.1 Hz.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600-ED Series and is the answer not in the manual?

SMC Networks EX600-ED Series Specifications

General IconGeneral
BrandSMC Networks
ModelEX600-ED Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals