IO-Link master unit parameters (continued)
No.
Parameter
Definition
Item
Content
Default
setting
Parameter
setting range
9
Port cycle time
Setting for
communication
cycle time with IO-
Link device.
As fast as
possible
(AFAP)
Communicate at the
fastest speed based on
the IO-Link device’s
minimum cycle time.
Channel
0.4 to 132.8ms
Communicates at set
intervals.
10
Vendor ID
Setting for vendor
ID which is
compared when
the IO-Link device
comparison
function is valid.
0x0000
to
0xFFFF
Set the vendor ID of the
device to be connected.
0x0001
Channel
11
Device ID
Setting for device
ID which is
compared when
the IO-Link device
comparison
function is valid.
0x000000
to
0xFFFFFF
Set device ID of the
device to be connected.
0x000001
Channel
1: Since “Hold/Clear setting switch” is not reflected, use these parameters to set the output behavior during EtherCAT
®
communication
error and idling. Refer to “Output setting when the EtherCAT
®
communication error/idling occurs” (page 74) for difference in
operation of the connected device due to settings.
2: Some PLC does not support an idle mode.
3: The availability of the byte swap parameters depends on the process data size of the device to be connected.
Refer to “I/O byte swap function” (page 74) for details.
4: Valid only the PortMode is in “IOL_Manual”.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600-ED Series and is the answer not in the manual?

SMC Networks EX600-ED Series Specifications

General IconGeneral
BrandSMC Networks
ModelEX600-ED Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals