-72-
No. DOC1045423
IO-Link master unit parameters (continued)
No.
Parameter
Definition
Item
Content
Default
setting
Parameter
setting range
5
Idle output
(DO_C/Q)
1 2
Setting for digital
outputs signal
behavior when
EtherCAT
®
communication
idling is detected.
Clear
Turn OFF the digital
output.
Unit
Hold
Maintain the digital output
that the IO-Link master
finally receives.
ForceON
Turn ON the digital output.
6
Byte swap
3
Swap the byte order
of the process data,
which is exchanged
between EtherCAT
®
communication and
IO-Link master.
Direct
(No Swap)
Data order is not swapped.
Unit
Swap 16 bit
Swapped by word.
Swap 32 bit
Swapped by double word.
Swap All
All bytes swapped.
7
Port mode
Setting the
operation mode for
each port.
Deactivated
Deactivate the port.
Channel
IOL_Manual
Start-up IO-Link
communication based on
the IO-Link device
comparison function.
IOL_Autostart
Start up the IO-Link
communication without
comparing IO-Link device.
DI_C/Q
Digital input only.
DO_C/Q
Digital output only.
8
Validation
& Backup
4
Setting for the
connected device
comparison function
(comparison of
vendor ID and
device ID)
And
setting for the data
storage (DS).
No check
Comparison function: invalid
DS function: invalid
Channel
Type compatible
Device V1.0
Connected device: V1.0
Comparison function: valid
DS function: invalid
Type compatible
Device V1.1
Connected device: V1.1
Comparison function: valid
DS function: invalid
Type compatible
Device V1.1,
Backup+Restore
Connected device: V1.1
Comparison function: valid
DS function: Valid (Backup
& restore)
Type compatible
Device V1.1,
Restore
Connected device: V1.1
Comparison function: valid
DS function: valid
(for restore only)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600-ED Series and is the answer not in the manual?

SMC Networks EX600-ED Series Specifications

General IconGeneral
BrandSMC Networks
ModelEX600-ED Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals