BURNER SPECIFICATIONS
Table 5
Carlin
Burner Burner Pump Slide Bar
Boiler Capacity Input Burner Nozzle Pressure Or Head Air
Model (GPH) (MBH) Model Type (PSI) Position Setting
3L .75 105 EZ-1 HP .65 70A Delavan 150 .60-.65 .65
3H .95 133 EZ-1 HP .75 70B Delavan 150 .75 .75
4L 1.10 154 EZ-1 HP .85 60B Delavan 150 .85-1.00 .85
4H 1.25 175 EZ-1 HP 1.00 60B Delavan 150 .85-1.00 1.00
5L 1.40 196 EZ-1 HP 1.10 60B Delavan 150 1.10-1.25 1.10
5H 1.70 238 EZ-1 HP 1.25 60B Delavan 150 1.10-1.25 1.25
6L 1.75 245 99 FRD 1.75 60R Monarch 100 5 70%
6H 2.10 294 99 FRD 2.10 60R Monarch 100 6 100%
Beckett
Burner Burner Pump
Boiler Capacity Input Burner Nozzle Pressure Air Air Ret.
Model (GPH) (MBH) Model Type PSI Shutter Band Head
3L .75 105 AFG 0.65 80A Delavan 140 9 2 F3
3H .95 133 AFG 0.75 80A Delavan 140 10 4 F3
4L 1.10 154 AFG 0.85 80A Delavan 140 9 0 F6
4H 1.25 175 AFG 1.00 80A Delavan 140 10 1 F6
5L 1.40 196 AFG 1.10 80A Delavan 140 10 2 F6
5H 1.70 238 AFG 1.35 80B Delavan 140 10 4 F12
6L 1.75 245 AFG 1.50 80B Delavan 140 10 3 F12
6H 2.10 294 AFG 1.65 80B Delavan 140 10 4 F16
Reillo 40 Series Oil Burners
Burner Burner Reillo Pump Air
Boiler Capacity Input Burner Nozzle Pressure Turbulator Gate
Model (GPH) (MBH) Model Type PSI Setting Setting
3L .75 105 F3 0.60 60W Delavan 160 1.5 2.7
3M .85 119 F3 0.65 60W Delavan 160 3.0 2.7
3H .95 133 F3 0.75 60W Delavan 160 3.0 2.7
4L 1.10 154 F5 0.85 60W Delavan 150 1.0 3.4
4H 1.25 175 F5 1.00 60W Delavan 150 1.5 4.0
5L 1.40 196 F5 1.20 60W Delavan 150 2.0 2.5
5H 1.70 238 F10 1.35 60W Delavan 145 1.0 3.0
6L 1.75 245 F10 1.35 60W Delavan 145 1.0 3.0
6H 2.10 294 F10 1.50 60W Delavan 145 3.0 3.0
Notes
All the burner settings listed are approximate. Every burner should be tuned with instruments by a trained technician.
CO
2
should be 11 1/2 - 13 1/2% with “0” smoke. The overfi re draft should be -.02 to -.05. If the overfi re draft exceeds -.05
a single acting barometric should be used.
Beckett Burners: All are equiped with F style combustion heads. A 3-3/8" Static Plate is installed on all burner sizes except
6H. A Low Firing Rate Baffl e is installed only on 3L, 3H burners.
Riello: An ST Air Tube Combo is used on all models. The insertion depth is 3-3/4".