8. 9. Unit EnabLEd controLs tabLE: addrEss 0x1150; 1 words
Code Description Bit Address Remarks
V007 Eco-mode 7 0x1150
V008 Normal-mode 8
V032 Unit Start procedure 0 0x1152
V033 Reserved 1
V034 Make unit available 2
V035 Switch load to inverter 3
V036 Switch load to mains 4
V037 Switch off unit output 5
V038 6
V039 7
V040 Rectier on 8
V041 Rectier off 9
V042 Inverter on 10
V043 Inverter off 11
V044 12
V045 Battery test 13
8. 10. controLs sEnd to UPs: addrEss 0x1190, writE 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using ADICOM interface.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not allowed,
the function will be ignored. Controls available by MODBUS connection:
Code Description Bit To Write Address Remarks
C007 Eco-mode 7 0x1190
C008 Normal-mode 8
C032 Unit Start procedure 0 0x1192
C033 Reserved 1
C034 Make unit available 2
C035 Switch load to inverter 3
C036 Switch load to mains 4
C037 Switch off unit output 5 LOAD OFF IMMEDIATE!!
C038 6
C039 7
C040 Rectier on 8
C041 Rectier off 9
C042 Inverter on 10
C043 Inverter off 11
C044 12
C045 Battery test 13
C046 14
C047
C048
Reset alarm 0 0x1193
sIngle UnIt UPs modbUs tables
20
Delphys green power - Ref.:
IOMDGPJB0910-GB_11