Do you have a question about the socomec Green Power 2.0 and is the answer not in the manual?
Guidelines for using the JBUS/MODBUS interface and ensuring repairs are done by trained staff.
Emphasizes respecting safety requirements and referring to operating instructions.
Identifies the 'Com-Slots' as the location for communication interfaces within the UPS.
Instructs to plug the serial interface into slot 2 and secure it with screws.
Details MODBUS serial link interface usage in parallel systems and bypass configurations.
Specifies the pinout for RS232 connection, including standard PC connections.
Describes the 2-wire connection for RS485, including dip-switch settings for terminal resistors.
Details the 4-wire connection for RS422, including dip-switch settings for terminal resistors.
Identifies the 'Com-Slots' as the location for communication interfaces within the UPS.
Lists default settings for COM2 serial link: 9600 bauds, NONE parity, 8 data bits, 1 stop bit, slave 1.
Guidance on reading identification, status, and alarm tables completely, and measurements by word or group.
Illustrates the structure of incoming data, showing word and bit composition.
Details the UPS identification parameters, including description, address, and type.
Lists unit alarm codes, their bit positions, addresses, and descriptions for identifying operational issues.
Provides a comprehensive table of unit measurements, including voltage, current, power, and frequency.
Lists available controls for the UPS, including their bit positions and addresses.
Identifies the 'Com-Slots' as the location for communication interfaces within the UPS.
Presents the MODBUS table for modular parallel systems, showing start addresses, length, and functions.
Provides UPS measurement data for modular systems, covering voltages, currents, and powers.
Presents the MODBUS table for centralized bypass systems, detailing addresses, length, and functions.
Lists UPS alarms for centralized bypass systems, including general alarms and bypass alarms.
Details bypass status bits, their addresses, and descriptions for monitoring bypass operations.
Provides bypass measurements, including voltage, current, power factor, and load rate.
Details module status bits, their addresses, and descriptions for monitoring module operational states.
Provides module measurement data, including voltages, currents, and power factors.
Information on accessing and configuring the MODBUS TCP card via its web interface.