5. 4. connEctions and wiring
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
5. 4.1. RS232 connection:
Standard PC connection
Sub-D 9 pins connector
Pin 2 : Rx
Pin 3 : Tx
Pin 5 : GND
5. 4.2. Isolated RS485 connection
2 wires connection
« dip-switch 1 » allows connecting the terminal resistor
Insulation via “opto-coupler”
2 polarization resistors could be removed easily (if needed).
5. 4.3. Isolated RS422 connection
4 wires connection
« dip-switch 1 and 2 » allows connecting the terminal
resistor
Insulation via “opto-coupler”
4 polarization resistors could be removed easily (if needed).
RTX +
RTX -
TX -
RX -
TX +
RX +
Before making any connection, please check the cabling. A wrong connection or cabling can damage
the serial link interface.
the shield should be earthing at one point.
the shield should be earthing at one point.
InstallatIon InsIde UPs
7
Delphys green power - Ref.:
IOMDGPJB0910-GB_11
ENGLISH