3.6. User settings
The following table displays the options that can be changed by the user.
SUBMENU AVAILABLE SETTINGS DEFAULT SETTINGS
Language
English, Italiano, Français, Deutsch, Español,
Português, Svenska, Русский, Polski, 简体中文
English
Audible alarm [enabled], [disabled] enabled
Output voltage [200V], [208V], [220V], [230V], [240V]
[230V]
[240V] for AU
Output frequency
In normal mode: [autosensing]
In converter mode: [50Hz], [60Hz]
autosensing
High efficiency mode [disabled], [enabled] disabled
Start/Restart
Cold start: [disabled], [enabled]
Auto restart: [disabled], [enabled]
Start on bypass: [disabled], [enabled]
enabled
enabled
disabled
Site wiring fault [enabled], [disabled] disabled
Overload pre-alarm [50%~105%] 105%
External battery
[Auto detection],
[Manual Ah: 7~144Ah]
Auto detection
0 Ah
Charger current [2A], [4A], [6A], [8A] for long backup model 4A
Dry in Signal [Disabled], [Remote on], [Remote off], [Forced bypass] disabled
Dry out Signal
[load powered], [on bat], [Low bat], [bat open],
[bypass], [ups ok]
bypass
Ambient temperature alarm [enabled], [disabled] enabled
Battery remaining time [enabled], [disabled] enabled
Backup time limit [enabled: 30min.~999min.], [disabled]
Standard: disabled
ES: enabled 60 min.
Date / Time dd/mm/yyyy hh:mm 01/01/2020 00:00
LCD contrast 0 - 100% 50%
Note: if the UPS is used in IT neutral systems, the site wiring fault
function should be disabled.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ITY3-TW030B and is the answer not in the manual?

socomec ITY3-TW030B Specifications

General IconGeneral
Product TypeUPS
Power Rating30 kVA
Frequency50/60 Hz
Form FactorTower
Battery TypeLead-Acid
Weight800 kg
TopologyOnline double conversion
Communication InterfaceRS232, USB
Operating Temperature0°C to 40°C
Power Capacity30 kVA
Output Power30 kW

Related product manuals