SOFAR 3.3~12KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 26 -
Figure 4-5 Incorrect connection between load and inverter
The resistance at connection point must less than 2 Ω . In case to have a
properly anti-islanding function, please choose the high-quality PV cable and
ensure the power loss is less than 1%. Meanwhile, the inverter AC side to grid
connection point must less than 100m. the relation between cable length, cross
section area and power loss as below:
Figure 4-6 relation between cable length, cross section area and power loss
The AC output terminal of this product is equipped with high current 5-core
terminal block and customized AC output waterproof cover, which can meet the
IP65 level requirements after installation. AC cable need customer self connect: