EasyManua.ls Logo

Sofar solar 15KTLX-G3 - User Manual

Sofar solar 15KTLX-G3
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Shenzhen SOFARSOLAR Co., Ltd.
Solar Grid-tied Inverter
Product Model: SOFAR 15~24KTLX-G3
User manual

Questions and Answers

  • W
    William GordonAug 14, 2025
    What causes Reserved (ID113) error on Sofar solar 15KTLX-G3?
    • B
      Brandon WagnerAug 14, 2025
      Check if the ambient temperature of the installation position exceeds the upper limit. If it does, improve ventilation to decrease the temperature. Also, check whether the inverter has dust and whether there are foreign matters blocking the fan at the air inlet.
  • S
    Sarah HughesAug 17, 2025
    What causes CT Disconnect error on Sofar solar Inverter?
    • W
      william22Aug 17, 2025
      Check the wiring of input, output and communication according to the user's manual. If the use method is not ruled out, please contact the new energy customer service of Capital Airlines.
  • G
    gordonnicholsonAug 21, 2025
    What to do if Sofar solar Inverter GridUVP alarm occurs frequently?
    • A
      Adrienne YoungAug 21, 2025
      If the GridUVP alarm occurs frequently, first check if the grid voltage/frequency is within the acceptable range. If it is not, contact technical support. If the voltage/frequency is ok, check the AC circuit breaker and AC wiring of the inverter.
  • M
    Michael HawkinsAug 25, 2025
    Why does my Sofar solar 15KTLX-G3 show GridOVP?
    • J
      John GuzmanAug 25, 2025
      If the GridOVP alarm occurs occasionally, it is likely due to occasional abnormalities in the electric grid. The inverter will automatically return to normal operation when the electric grid stabilizes.
  • B
    boyddanielAug 27, 2025
    What to do if Sofar solar 15KTLX-G3 Inverter shows GridOFP repeatedly?
    • H
      hunter54Aug 27, 2025
      If the grid voltage/frequency is within the acceptable range and AC wiring is correct, while the GridOFP alarm occurs repeatedly, contact technical support to change the grid over-voltage, under-voltage, over frequency, under-frequency protection points after obtaining approval from the local electrical grid operator.
  • C
    Christopher EstradaAug 31, 2025
    How to fix FanFault1 on Sofar solar 15KTLX-G3?
    • N
      nshieldsAug 31, 2025
      Check the inverter for dust and foreign objects blocking the fan at the air inlet. If found, improve the ventilation and heat dissipation of the environment.
  • E
    Emily MillerSep 2, 2025
    What to do if Sofar solar 15KTLX-G3 displays OVRT?
    • J
      James BurkeSep 3, 2025
      If your Sofar solar Inverter displays OVRT, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If not, contact technical support.
  • S
    Scott BlanchardSep 6, 2025
    What to do if Sofar solar 15KTLX-G3 Inverter displays unrecoverH wAcOCP?
    • H
      hollycaseySep 6, 2025
      If your Sofar solar Inverter displays unrecoverH wAcOCP, turn OFF the “DC switch”, wait for 5 minutes, then turn ON the “DC switch”. Check whether the fault is rectified. If not, contact technical support.
  • C
    Charles CrossSep 10, 2025
    Why does my Sofar solar 15KTLX-G3 show BusUVP?
    • S
      Steven HicksSep 10, 2025
      If the configuration of the PV array is correct, the BusUVP error could be because the sun irradiation is too low. Once sun irradiation returns to normal, the inverter will work normally again.

Summary

Basic Safety Information

Installation and Maintenance Requirements

Outlines compliance with laws, reading instructions, and contacting local utility/service.

Qualified Personnel and Location Requirements

Specifies requirements for qualified electricians and suitable installation sites.

Transportation and Electrical Connection Safety

Covers safe handling during transport and essential electrical connection precautions.

Maintenance, EMC, and Symbols Explanation

Details maintenance, EMC/noise levels, and explains symbols and signs.

Installation

Installation Safety Precautions

Highlights critical safety warnings regarding installation procedures and conditions.

Installation Process and Preparation

Outlines the overall installation flow and pre-installation checks, including parts verification.

Electrical Connection

Electrical Connection Safety Precautions

Emphasizes critical safety warnings before performing electrical connections.

AC Output Connection

Provides detailed steps for connecting the inverter to the grid's AC side.

DC Input Connection

Guides on connecting the PV array's DC input to the inverter.

Commissioning of Inverter

Operation Interface

Trouble shooting and Maintenance

Troubleshooting Guide

Provides general tips for identifying and resolving potential errors.

Fault Code List and Solutions

Lists common fault IDs, their reasons, and suggested solutions.

Sofar solar 15KTLX-G3 Specifications

General IconGeneral
Model15KTLX-G3
TypeGrid-tied Inverter
Max. DC Input Power22.5 kW
Max. DC Voltage1100 V
Start Voltage200 V
MPPT Voltage Range200-1000 V
Number of MPPTs2
Number of DC Inputs per MPPT2
Rated AC Power15 kW
Rated Grid Frequency50/60 Hz
THDi< 3%
Max. Efficiency98.6%
DC SwitchYes
Protection ClassIP65
Max. AC Power16500 W
AC Voltage Range180-280 V
Power Factor Adjustment Range0.8 leading to 0.8 lagging
Operating Temperature Range-25°C to +60°C
CommunicationRS485
CoolingNatural cooling

Related product manuals