Solamiser User Manual
Note: Solamiser does not have an internal fuse or
circuit breaker as circuit protection is provided by
the consumer unit's immersion heater circuit
breaker. The rating of this circuit breaker should
not exceed 16 A.
f) Connect the brown core of the five core cable
between Solamiser terminal Marked L and the
consumer unit immersion heater circuit breaker
output.
g) Connect the blue core of the five core cable
between Solamiser terminal marked N to the
consumer unit neutral busbar.
h) Connect the yellow and green core of the five
core cable between Solamiser heat sink mounting
screw marked E and the the consumer unit's earth
busbar.
i) Connect the black core of the five core cable
between Solamiser terminal Marked H1 and the
previously disconnected immersion heater cable
inside of the consumer unit. This can be done with
a suitable in-line crimp connector.
j) If you have a second load, such as a storage
heater that Solamiser can switch, the power cable
of this device should also be routed to the
12