Table of Contents

Questions and Answers

  • M
    Mary KhanAug 17, 2025
    What to do if my SolarEast BLN-010TD1 shows E03 water flow error?
    • D
      David MccallAug 17, 2025
      To troubleshoot a SolarEast Heat Pump experiencing an E03 error (water flow switch failure or low water flow protection), follow these steps: * Ensure the pipeline valve is fully open to allow clear water flow. * Verify the water flow switch is correctly installed and the model is appropriate. * Confirm the water flow switch connection line is inserted into the correct port (D13 white). * Check that the circulating water pump is functioning normally and the water system isn't blocked. * Assess the water pump's head and flow; if insufficient, consider adding a hot water auxiliary pump. * Ensure the external auxiliary pump is not reversed.
  • Q
    qlopezAug 22, 2025
    What to do if my SolarEast BLN-010TD1 displays E06 Low voltage switch failure?
    • C
      christina98Aug 22, 2025
      If your SolarEast Heat Pump is showing error code E06, indicating a low voltage switch failure, here are the steps you can take to resolve the issue: 1. Check the low-pressure pressure switch for any damage and ensure the wiring terminals are correctly connected (low voltage switch D12 blue). 2. Use a pressure gauge to connect to the low-pressure inspection port and measure if there is a refrigerant leak in the system. After supplementing the refrigerant, use foam to check for refrigerant leakage at the welding joint of the copper pipe. 3. Verify that the fan is operating normally. 4. Inspect the system for blockages by connecting a pressure gauge to both the high and low-pressure inspection ports simultaneously to measure whether the operating pressure of the system is normal.
  • K
    Kayla JenningsAug 25, 2025
    What to do if SolarEast Heat Pump shows E12 Exhaust temperature too high protection?
    • P
      Phyllis HensleyAug 26, 2025
      To address an E12 error (Exhaust temperature too high protection) on your SolarEast Heat Pump: 1. Check the system for blockages or insufficient refrigerant. Use a pressure gauge to connect to the high and low pressure inspection ports to measure the operating pressure of the system. 2. Check if the exhaust gas temperature sensor is damaged. Use a multimeter to measure the resistance value (T3 red port).
  • M
    Melissa PhamAug 27, 2025
    What to do if my SolarEast Heat Pump displays error E37?
    • J
      Jamie RodriguezAug 27, 2025
      To resolve the E37 error (Too large temperature difference between inlet and outlet water protection) on your SolarEast Heat Pump, you can take the following steps: 1. Make sure that the pipeline valve is fully open. 2. Check if the water pump is working. 3. Check the rated head of the pump and whether the rated flow meets the requirements for normal operation of the machine. 4. Manually drain the drain pump and pipe air.
  • B
    baileydonnaAug 30, 2025
    What to do if SolarEast Heat Pump shows E02 Phase loss fault?
    • K
      Kari AguilarAug 30, 2025
      If your SolarEast Heat Pump displays error E02 (Phase loss fault), take these steps: 1. Ensure the power cord is securely connected. 2. Use a multimeter to check for 220V voltage between the neutral wire and each live wire while the power is on. 3. Use a multimeter to check for 380V voltage between the three live wires while the power is on. Note that 220V machines will not experience this failure.
  • C
    conniegarciaSep 2, 2025
    How to fix SolarEast BLN-010TD1 E01 wrong phase protection?
    • C
      Carol RobinsonSep 2, 2025
      If your SolarEast Heat Pump shows E01 (wrong phase protection) error, the solution is to exchange any two of the three live wires (R, S, T) and then power on the machine again. Note that 220V machines will not have this failure.
  • R
    Ryan HarperSep 4, 2025
    What to do if my SolarEast BLN-010TD1 Heat Pump shows E09 Communication failure?
    • B
      barbaramosleySep 4, 2025
      To address an E09 error (Communication failure between the wire controller and the main board) on your SolarEast Heat Pump: 1. Check whether the communication between the wire controller and the main board is normal. 2. Use a multimeter to measure whether the voltage output of the motherboard port is normal (white port).
  • R
    Rachel LivingstonSep 7, 2025
    What to do if SolarEast BLN-010TD1 shows E15 Inlet water temperature sensor failure?
    • L
      Lori MedinaSep 8, 2025
      To troubleshoot an E15 error (Inlet water temperature sensor failure) on your SolarEast Heat Pump, consider the following: 1. Check if the sensor connection line is open or disconnected. 2. The sensor may be damaged. 3. The motherboard port may be damaged. 4. Use a multimeter to measure whether the resistance is correct (T8 white port).
  • R
    Ronald GriffinSep 10, 2025
    What to do if SolarEast BLN-010TD1 displays E16 Coil sensor failure?
    • A
      alawrenceSep 10, 2025
      To troubleshoot an E16 error (Coil sensor failure) on your SolarEast Heat Pump, you can check the following: 1. See if the sensor connection line is open or disconnected. 2. The sensor might be damaged. 3. The motherboard port could be damaged. 4. Use a multimeter to measure whether the resistance value is correct (TI red port).
  • B
    Brett AndersonSep 13, 2025
    What to do if my SolarEast Heat Pump shows E18 Exhaust sensor failure?
    • E
      erin89Sep 13, 2025
      To resolve an E18 error (Exhaust sensor failure) on your SolarEast Heat Pump, check the following: 1. Ensure the sensor connection line is not open or disconnected. 2. Verify the sensor is not damaged. 3. Check that the motherboard port is not damaged. 4. Use a multimeter to measure whether the resistance is correct (TI red port).

Summary

1. Product Introduction

1.1. Product Model Pictures

Displays images of various SolarEast heat pump models for identification.

1.2. Parameter Table

Lists detailed technical specifications and operating parameters for each model.

1.3. Dimensions

Provides detailed dimensional drawings for various heat pump models.

1.4. Exploded View

Shows exploded views of heat pump unit components.

1.5. System Diagrams and Performance Curves

Presents system diagrams and performance curves for heat pumps.

2. Product Selection and Installation

2.1. Installation Instructions and Special Precautions

Provides essential instructions and precautions for installing heat pump units.

2.2. Installation Procedures

Covers general installation procedures and site requirements for the heat pump unit.

2.3. Pipeline and Water System Requirements

Covers pipeline installation, pressure testing, water quality, and insulation needs.

2.4. Electrical Wiring Precautions

Provides crucial precautions for electrical wiring connections and overall safety.

2.5. Room Heat Load Calculation and Unit Selection

Explains heat load calculation and guides on selecting heat pump units for floor heating.

3. Electrical Operation and Control

3.1. Unit Control Functions

Details various control functions and operational logic of the heat pump system.

3.2. Wire Controller Display and Operation

Guides on operating the wire controller, including settings and menus.

4. Error Diagnosis and Treatment

4.1. Maintenance Tools

Lists and describes essential tools required for unit maintenance and repairs.

4.2. Model Disassembly and Parts

Details the procedure for disassembling models and identifying specific parts.

4.3. Troubleshooting Common Fault Codes

Provides step-by-step troubleshooting guidance for common fault codes.

SolarEast BLN-010TD1 Specifications

General IconGeneral
BrandSolarEast
ModelBLN-010TD1
CategoryHeat Pump
LanguageEnglish

Related product manuals