BLN-006TB1/BLN-010TB1/BLN-014TB1/BLN-018TB1
BLN-010TB3/BLN-014TB3/BLN-018TB3/BLN-024TB3
Please read this manual carefully before using it and keep it in a safe place
Heat Pump for Heating & Cooling & DHW
Air Source Heat Pump
R32

Other manuals for SolarEast BLN-018TB1

Questions and Answers

  • B
    brandonfigueroaAug 16, 2025
    What to do if my SolarEast Heat Pump shows E03 water flow error?
    • C
      Cynthia CantrellAug 17, 2025
      To troubleshoot a SolarEast Heat Pump experiencing an E03 error (water flow switch failure or low water flow protection), follow these steps: * Ensure the pipeline valve is fully open to allow clear water flow. * Verify the water flow switch is correctly installed and the model is appropriate. * Confirm the water flow switch connection line is inserted into the correct port (D13 white). * Check that the circulating water pump is functioning normally and the water system isn't blocked. * Assess the water pump's head and flow; if insufficient, consider adding a hot water auxiliary pump. * Ensure the external auxiliary pump is not reversed.
  • W
    William EdwardsAug 22, 2025
    What to do if my SolarEast BLN-018TB1 displays E06 Low voltage switch failure?
    • S
      Shannon ClarkAug 22, 2025
      If your SolarEast Heat Pump is showing error code E06, indicating a low voltage switch failure, here are the steps you can take to resolve the issue: 1. Check the low-pressure pressure switch for any damage and ensure the wiring terminals are correctly connected (low voltage switch D12 blue). 2. Use a pressure gauge to connect to the low-pressure inspection port and measure if there is a refrigerant leak in the system. After supplementing the refrigerant, use foam to check for refrigerant leakage at the welding joint of the copper pipe. 3. Verify that the fan is operating normally. 4. Inspect the system for blockages by connecting a pressure gauge to both the high and low-pressure inspection ports simultaneously to measure whether the operating pressure of the system is normal.
  • O
    olivia03Aug 25, 2025
    What to do if SolarEast BLN-018TB1 Heat Pump shows E12 Exhaust temperature too high protection?
    • G
      Gregory MillerAug 26, 2025
      To address an E12 error (Exhaust temperature too high protection) on your SolarEast Heat Pump: 1. Check the system for blockages or insufficient refrigerant. Use a pressure gauge to connect to the high and low pressure inspection ports to measure the operating pressure of the system. 2. Check if the exhaust gas temperature sensor is damaged. Use a multimeter to measure the resistance value (T3 red port).
  • O
    owilsonAug 27, 2025
    What to do if my SolarEast BLN-018TB1 displays error E37?
    • K
      Kevin RushAug 27, 2025
      To resolve the E37 error (Too large temperature difference between inlet and outlet water protection) on your SolarEast Heat Pump, you can take the following steps: 1. Make sure that the pipeline valve is fully open. 2. Check if the water pump is working. 3. Check the rated head of the pump and whether the rated flow meets the requirements for normal operation of the machine. 4. Manually drain the drain pump and pipe air.
  • A
    Ashley WilliamsAug 30, 2025
    What to do if SolarEast BLN-018TB1 Heat Pump shows E02 Phase loss fault?
    • D
      Daniel DavisAug 30, 2025
      If your SolarEast Heat Pump displays error E02 (Phase loss fault), take these steps: 1. Ensure the power cord is securely connected. 2. Use a multimeter to check for 220V voltage between the neutral wire and each live wire while the power is on. 3. Use a multimeter to check for 380V voltage between the three live wires while the power is on. Note that 220V machines will not experience this failure.
  • J
    Jeremy CarrollSep 2, 2025
    How to fix SolarEast Heat Pump E01 wrong phase protection?
    • D
      djensenSep 2, 2025
      If your SolarEast Heat Pump shows E01 (wrong phase protection) error, the solution is to exchange any two of the three live wires (R, S, T) and then power on the machine again. Note that 220V machines will not have this failure.
  • R
    Roger BushSep 5, 2025
    What to do if my SolarEast BLN-018TB1 Heat Pump shows E09 Communication failure?
    • S
      Stephanie QuinnSep 5, 2025
      To address an E09 error (Communication failure between the wire controller and the main board) on your SolarEast Heat Pump: 1. Check whether the communication between the wire controller and the main board is normal. 2. Use a multimeter to measure whether the voltage output of the motherboard port is normal (white port).
  • A
    Anthony TurnerSep 7, 2025
    What to do if SolarEast Heat Pump shows E15 Inlet water temperature sensor failure?
    • N
      nfieldsSep 7, 2025
      To troubleshoot an E15 error (Inlet water temperature sensor failure) on your SolarEast Heat Pump, consider the following: 1. Check if the sensor connection line is open or disconnected. 2. The sensor may be damaged. 3. The motherboard port may be damaged. 4. Use a multimeter to measure whether the resistance is correct (T8 white port).
  • R
    Ronnie GillSep 10, 2025
    What to do if SolarEast BLN-018TB1 Heat Pump displays E16 Coil sensor failure?
    • J
      Jared JamesSep 10, 2025
      To troubleshoot an E16 error (Coil sensor failure) on your SolarEast Heat Pump, you can check the following: 1. See if the sensor connection line is open or disconnected. 2. The sensor might be damaged. 3. The motherboard port could be damaged. 4. Use a multimeter to measure whether the resistance value is correct (TI red port).
  • N
    nwrightSep 13, 2025
    What to do if my SolarEast BLN-018TB1 shows E18 Exhaust sensor failure?
    • A
      April GillSep 13, 2025
      To resolve an E18 error (Exhaust sensor failure) on your SolarEast Heat Pump, check the following: 1. Ensure the sensor connection line is not open or disconnected. 2. Verify the sensor is not damaged. 3. Check that the motherboard port is not damaged. 4. Use a multimeter to measure whether the resistance is correct (TI red port).

Summary

User Instructions

Precautions

Essential safety information and warnings for using the heat pump.

Operation Instruction

Installation

Heat Pump Installation

Requirements for the installation space and location of the heat pump.

Electrical Installation

Instructions and regulations for the safe electrical wiring and grounding of the unit.

Wire Diagram

Commissioning and Maintenance

Precautions Before Commissioning

Checklist of essential precautions before starting commissioning.

Commissioning

Steps and checks required for commissioning the heat pump.

Trouble Analysis

Specification

After-sale Service

Controller Supplement

Controller Manual

Detailed guide on using the controller for various functions and settings.

Temperature Compensation Curve

SolarEast BLN-018TB1 Specifications

General IconGeneral
BrandSolarEast
ModelBLN-018TB1
CategoryHeat Pump
LanguageEnglish