Questions and Answers

  • J
    James AshleyAug 17, 2025
    What to do if my SolarEast BLN-018TB3 Heat Pump shows E03 water flow error?
    • S
      Scott SchmidtAug 17, 2025
      To troubleshoot a SolarEast Heat Pump experiencing an E03 error (water flow switch failure or low water flow protection), follow these steps: * Ensure the pipeline valve is fully open to allow clear water flow. * Verify the water flow switch is correctly installed and the model is appropriate. * Confirm the water flow switch connection line is inserted into the correct port (D13 white). * Check that the circulating water pump is functioning normally and the water system isn't blocked. * Assess the water pump's head and flow; if insufficient, consider adding a hot water auxiliary pump. * Ensure the external auxiliary pump is not reversed.
  • O
    omeyerAug 23, 2025
    What to do if my SolarEast BLN-018TB3 Heat Pump displays E06 Low voltage switch failure?
    • M
      Martin TurnerAug 23, 2025
      If your SolarEast Heat Pump is showing error code E06, indicating a low voltage switch failure, here are the steps you can take to resolve the issue: 1. Check the low-pressure pressure switch for any damage and ensure the wiring terminals are correctly connected (low voltage switch D12 blue). 2. Use a pressure gauge to connect to the low-pressure inspection port and measure if there is a refrigerant leak in the system. After supplementing the refrigerant, use foam to check for refrigerant leakage at the welding joint of the copper pipe. 3. Verify that the fan is operating normally. 4. Inspect the system for blockages by connecting a pressure gauge to both the high and low-pressure inspection ports simultaneously to measure whether the operating pressure of the system is normal.
  • D
    Dr. Matthew Garcia DVMAug 26, 2025
    What to do if SolarEast BLN-018TB3 shows E12 Exhaust temperature too high protection?
    • S
      Samantha ThompsonAug 26, 2025
      To address an E12 error (Exhaust temperature too high protection) on your SolarEast Heat Pump: 1. Check the system for blockages or insufficient refrigerant. Use a pressure gauge to connect to the high and low pressure inspection ports to measure the operating pressure of the system. 2. Check if the exhaust gas temperature sensor is damaged. Use a multimeter to measure the resistance value (T3 red port).
  • T
    Toni BallardAug 28, 2025
    What to do if my SolarEast BLN-018TB3 Heat Pump displays error E37?
    • A
      Andrew KhanAug 28, 2025
      To resolve the E37 error (Too large temperature difference between inlet and outlet water protection) on your SolarEast Heat Pump, you can take the following steps: 1. Make sure that the pipeline valve is fully open. 2. Check if the water pump is working. 3. Check the rated head of the pump and whether the rated flow meets the requirements for normal operation of the machine. 4. Manually drain the drain pump and pipe air.
  • M
    Melanie TurnerAug 31, 2025
    What to do if SolarEast Heat Pump shows E02 Phase loss fault?
    • V
      Vickie GreerAug 31, 2025
      If your SolarEast Heat Pump displays error E02 (Phase loss fault), take these steps: 1. Ensure the power cord is securely connected. 2. Use a multimeter to check for 220V voltage between the neutral wire and each live wire while the power is on. 3. Use a multimeter to check for 380V voltage between the three live wires while the power is on. Note that 220V machines will not experience this failure.
  • S
    Sarah WilkinsSep 2, 2025
    How to fix SolarEast BLN-018TB3 Heat Pump E01 wrong phase protection?
    • H
      Heidi SawyerSep 2, 2025
      If your SolarEast Heat Pump shows E01 (wrong phase protection) error, the solution is to exchange any two of the three live wires (R, S, T) and then power on the machine again. Note that 220V machines will not have this failure.
  • J
    James BenitezSep 5, 2025
    What to do if my SolarEast Heat Pump shows E09 Communication failure?
    • D
      Daisy MontesSep 6, 2025
      To address an E09 error (Communication failure between the wire controller and the main board) on your SolarEast Heat Pump: 1. Check whether the communication between the wire controller and the main board is normal. 2. Use a multimeter to measure whether the voltage output of the motherboard port is normal (white port).
  • S
    Sean RobertsSep 8, 2025
    What to do if SolarEast BLN-018TB3 Heat Pump shows E15 Inlet water temperature sensor failure?
    • S
      Sharon WellsSep 8, 2025
      To troubleshoot an E15 error (Inlet water temperature sensor failure) on your SolarEast Heat Pump, consider the following: 1. Check if the sensor connection line is open or disconnected. 2. The sensor may be damaged. 3. The motherboard port may be damaged. 4. Use a multimeter to measure whether the resistance is correct (T8 white port).
  • D
    donnamercadoSep 12, 2025
    What to do if SolarEast Heat Pump displays E16 Coil sensor failure?
    • J
      Jeffrey LongSep 12, 2025
      To troubleshoot an E16 error (Coil sensor failure) on your SolarEast Heat Pump, you can check the following: 1. See if the sensor connection line is open or disconnected. 2. The sensor might be damaged. 3. The motherboard port could be damaged. 4. Use a multimeter to measure whether the resistance value is correct (TI red port).
  • K
    Kathy HuffSep 13, 2025
    What to do if my SolarEast BLN-018TB3 shows E18 Exhaust sensor failure?
    • A
      Amy SwansonSep 13, 2025
      To resolve an E18 error (Exhaust sensor failure) on your SolarEast Heat Pump, check the following: 1. Ensure the sensor connection line is not open or disconnected. 2. Verify the sensor is not damaged. 3. Check that the motherboard port is not damaged. 4. Use a multimeter to measure whether the resistance is correct (TI red port).

Summary

User Instructions

Precautions

General safety guidelines and warnings for using the heat pump.

Refrigerant Precautions

Refrigerant Handling and Storage

Guidelines for safe storage, installation, and handling of refrigerants.

Flammable Refrigerant Requirements

Servicing and Repair Safety Procedures

Safety procedures for working with flammable refrigerants, including ignition sources and ventilation.

Temperature and Climate Curve Setting

Wi-Fi Setup and Connectivity

Installation Preparation

Heat Pump Installation Space Requirements

Guidelines for selecting an appropriate installation location and space for the unit.

Installation Precautions

Important safety considerations and warnings during unit installation.

Electrical Installation and Wiring

General Electrical Installation Guidelines

Requirements for electrical installation, grounding, and wiring.

Mainboard Output Definitions

Expansion Board Output Definition

Wire Diagram

Commissioning and Maintenance Procedures

Pre-Commissioning Checks

Essential checks to perform before starting the commissioning process.

Commissioning Process

Steps and checks for commissioning the heat pump unit.

Operational Status and Protection Features

Routine Maintenance

Trouble Analysis and Fault Codes

Fault Code Descriptions (E01-E06)

Detailed descriptions and causes for error codes E01 through E06.

Fault Protection and Maintenance Instructions

Technical Specifications

Controller Operation Manual

Temperature Compensation Curves