EasyManua.ls Logo

SolarEdge SE2200

SolarEdge SE2200
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SE15K SE16K SE17K SE25K SE27.6K SE33.3K Unit
Residual current
detector / Residual
Current step detector
300 / 30 mA
Grid supported
three phase
3 / N / PE (WYEwith Neutral) V
Inrush current AC
(Peak/ Duration)
3/ 20 3.1/ 20 4.2/ 20
Aac
(rms) /
ms
Maximum output
fault current
40 63 A
Power factor range
1 (adjustable from -0.9 to
+0.9)
1 (adjustable from -0.8 to
+0.8)
(1)
Total harmonic
distortion
< 3%
Protective class Class I
Utility monitoring,
islanding protection,
configurable Power
Factor, country
configurable
thresholds
Yes
Overvoltage category III
Input
Maximum DC power
(Module STC)
20250 21600 22950 33750 37250 45000 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
900 1000 Vdc
Nominal DC input
voltage
750 840 Vdc
Maximum input
current
22 23 23 37 40 40 Adc
Maximum back-feed
current
0 Adc
(1)
For SE27.6K - when set to Germany Power Factor is limited to 0.9.
Technical Specifications - Three Phase Inverters (Europe &APAC) 109
Three Phase System Installation Guide MAN-01-00057-4.1

Table of Contents

Related product manuals