When the inverter is operated in 3-phase application, set up
inverter to be operated in specific phase.
L1 phase:
L2 phase:
L3 phase:
29
Low DC cut-off voltage or
Low SOC:
If battery power is only
power source available,
inverter will shut down.
If PV energy and battery
power are available,
inverter will charge
battery without AC
output.
If PV energy, battery
power and utility are all
available, inverter will
transfer to line mode
and provide output
power to loads.
default: 44.0V
If self-defined is selected in
program 5, this program can be
set up. Setting range is from
42.0V to 48.0V. Increment of each
click is 0.1V. Low DC cut-off
voltage will be fixed to setting
value no matter what percentage
of load is connected.
SOC 0% (default for Lithium)
If any types of lithium battery is
selected in program 05, setting
value will change to SOC
automatically. Adjustable range
is 0% to 90%. Increment of each
click is 5%.
30 Battery equalization
Battery equalization
Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
31 Battery equalization voltage
default: 58.4V
Setting range is from 48.0V to
62.0V. Increment of each click is
0.1V.