22
Beeps while primary source
is interrupted
Alarm on (default)
Alarm off
23
Overload bypass:
When enabled, the unit will
transfer to line mode if
overload occurs in battery
mode.
Bypass disable (default)
Bypass enable
25 Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
default: 56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 48.0V to 62.0V. Increment of each click
is 0.1V.
27 Floating charging voltage
default: 54.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 48.0V to 62.0V. Increment of each click
is 0.1V.
28
AC output mode
*This setting is only
available when the inverter
is in standby mode (Switch
off).
Single: This inverter is used
in single phase application.
Parallel: This inverter is operated
in parallel system.