Parameter Setting
19
Setting the wiring mode
Setting the wiring mode to 3-phase 4-wire (3P4W) or 3-phase 3-wire (3P3W).
Setting the metering mode
Set the metering mode to phase metering or net metering. For net metering, the screen
will display an 1 on the Imp/Exp status bar.
Metering mode Screen display Description
Phase metering
The power of each phase is counted separately
into feed-in energy or consumed energy.
For example, in an hour, if phase A and B
respectively deliver 1 kW energy to the grid,
and phase C receives 1 kW from the grid, the
displayed export energy will be 2 kWh, and the
import energy be 1 kWh.
Sum metering
The total feed-in power is counted into feed-in
energy or consumed energy. For example, in an
hour, if phase A and B respectively deliver 1 kW
energy to the grid, and phase C receives 1 kW
from the grid, the displayed export energy will
be 1 kWh, and the import energy be 0 kWh.