THERMOCUBE 200/300/400 THERMOELECTRIC CHILLER MANUAL 52-11300-1
SOLID STATE COOLING SYSTEMS, 167 MYERS CORNERS ROAD, WAPPINGERS FALLS, NY 12590 5
TELEPHONE: (845) 296-1300 FAX: (845) 296-1303 WEB: WWW.SSCOOLING.COM VERSION M28
SECTION 2
S
PECIFICATIONS _________________________________________________
Operating Range (Set Point): 5°C to 50°C standard
(down to -5°C with low temp option - LT)
(up to 65°C with high temp option – HT, 60°C for centrifugal pumps)
Ambient Temperature Range: 0°C to 40°C non-condensing
Stability / Repeatability: ±0.05°C with constant load (even near ambient)
Cooling Capacity (typical
1
): 200, 300 or 400 Watts @ 20°C in 20°C ambient air
Heating Capacity (typical): 400, 600 or 800 Watts @ 20°C in 20°C ambient air
Noise Level (at 1 meter): < 63 dBA (down to 49 dBA with “-VS” variable speed fan option)
Coolant / Process Fluid: Koolance (27% propylene glycol / water mix)
or 27-50% ethylene glycol / water mix
Options available for PAO, Fluorinert / Galden or HFE
(contact SSCS for advice on other fluids)
Process Fluid Fittings: 1/4” John Guest standard (see options section for other fitting types)
Pumps: Diaphragm, Centrifugal or gear pumps available
(see options section for pump types and specifications)
Tank Volume: 300 ml with level sensor
Wetted Materials: Aluminum, stainless steel and polymers
or Copper, stainless steel and polymers (“-CU” option)
Dimensions (L x W x H): 13” x 11” x 13” (32cm x 28cm x 32cm)
Weight: 28 lbs (12.7 kg) – standard model
Power Input: Universal: 115-230 VAC, 50/60 Hz, 7-5 amps max
Controls: Digital PID controller for heating and cooling
Communications: Keypad or optional RS232 interface
Alarms Temperature, fluid level, system or component failure
(display and RS232 option)
Standards TUV listed to UL, CAN/CSA and EN 61010-1,
CE 61010-1
Other Options (see Section 7 for available options)
Warranty 2 years (diaphragm pumps are 1 year)
Note 1: Cooling capacity will vary with configuration.