44
Advanced Setup Table
Default = Factory Default Setting
Step# Description Pg# Range Default
66 Dry Contact Polarity 30 Open, Closed Open
67 Dry Contact Use 30 Condensate Pan, Occupied,
FDD, Holiday, Door Switch
68 Humidity Polarity 29 Open, Closed Open
69 Dehumidify Polarity 29 Open, Closed Open
70 Dehumidify only with Cooling 29 On, Off On
71 Skyport 30 On, Off On
72 Local API 30 On, Off Off
73 ADR 37 On, Off On
74 ADR Action 37 Observe Setpoint Observe
Offset, Observe Static Setpoint
Setpoints Offsets
75 Event Max Cool Setpoint 37 35 - 99 90
76 Event Min Heat Setpoint 37 35 - 99 50
77 Static Cool Setpoint 37 35 - 99 82
78 Static Heat Setpoint 37 35 - 99 60
79 Cool Setpoint Offset 38 1 to 10 4
80 Heat Setpoint Offset 38 -1 to -10 -4
81 Press Fan To Clear All Messages 33