Parameter F (Fan Parameter)
Normally, in heating mode or cooling mode, fan will start up 10s ahead of compressor and 30s later to shut off.
1. Fast mute function
When the fast mute function is turned on, the fan will run according to the parameter F13 if it needs to be turned on, and exit the
mute function after 8 hours. The manual operation of fast mute during the timing mute will result in the time mute failure.
2. When F10=1, enable the timing mute function.
During the time of F11-F12 (including F11, excluding F12), if the fan needs to be turned on, it will run according to the parameter
F13. If the fan needs to be turned on at other times, the speed will be controlled according to the suction pressure and exhaust
pressure.
3. During the period that the mute function is performed, if high /low voltage protection occurs in any system:
① Automatic exit fast mute function;
② Permanently exit the timer mute function, and will be restored until the power is reenergized.