SIM Inverter Monobloc Air-to-Water Heat Pump
Address Function HEX Number Content Description Remark
1049 03/16/06 419 Reserved
1050 03/16/06 41A Reserved
1051 03/16/06 41B Reserved
1052 03/16/06 41C Reserved
1053 03/16/06 41D Reserved
1054 03/16/06 41E Reserved
1055 03/16/06 41F Reserved
1056 03/16/06 420 Reserved
1057 03/16/06 421 Reserved
1058 03/16/06 422 Reserved
1059 03/16/06 423 F01 Maximum fan speed setting during heating 0-2000r DIGI1
1060 03/16/06 424 F02 Fan minimum speed set value during heating 0-2000r DIGI1
1061 03/16/06 425 F03
Maximum fan speed during heating corresponding to low
return air pressure
0-20bar TEMP1
1062 03/16/06 426 F04
Minimum fan speed during heating corresponds to the
high return air pressure
0-20bar TEMP1
1063 03/16/06 427 F05 Maximum fan speed setting during cooling 0-2000r DIGI1
1064 03/16/06 428 F06 Fan minimum speed set value during cooling 0-2000r DIGI1
1065 03/16/06 429 F07
Maximum fan speed during cooling corresponding to low
return air pressure
0-50bar TEMP1
1066 03/16/06 42A F08
Minimum fan speed during cooling corresponds to the
high return air pressure
0-50bar TEMP1
1067 03/16/06 42B F09 Manual fan speed 0~2000r DIGI1
1068 03/16/06 42C F10 Whether enable the timer mute function (0-no/1-yes) DIGI1
1069 03/16/06 42D F11 Timed mute start time 0~23h DIGI1
1070 03/16/06 42E F12 Timed mute end time 0~23h DIGI1
1071 03/16/06 42F F13 Mute speed 300~1300r DIGI1
1072 03/16/06 430 F14 DC fan rated speed 600r DIGI1
1073 03/16/06 431 F15 Fan type 0~2 (0-Single speed fan, 1-DC single fan, 2-DC double fan) DIGI1
1074 03/16/06 432 One-click mute 0-off/1-on DIGI1
1075 03/16/06 433 Reserved
1076 03/16/06 434 Reserved
1077 03/16/06 435 Reserved
1078 03/16/06 436 Reserved
1079 03/16/06 437 Reserved
1080 03/16/06 438 Reserved
1081 03/16/06 439 Reserved
1082 03/16/06 43A Reserved
1083 03/16/06 43B Reserved
1084 03/16/06 43C Reserved
1085 03/16/06 43D Reserved
1086 03/16/06 43E Reserved
1087 03/16/06 43F Reserved
1088 03/16/06 440 Reserved
1089 03/16/06 441 Reserved
1090 03/16/06 442 Reserved
1101 03/16/06 44D D01 Coil temperature for heating exit defrost 1~40°C TEMP1
1102 03/16/06 44E D02 Corresponding pressure value for heating exit defrost 1~25bar TEMP1
1103 03/16/06 44F D03 Heating defrost cycle 1~90Min DIGI1
1104 03/16/06 450 D04 Heating defrost longest time 1~20Min DIGI1
1105 03/16/06 451 D05 Slip into low pressure high point 1~20bar TEMP1
1106 03/16/06 452 D06 Slip into low pressure low point 1~20bar TEMP1
1107 03/16/06 453 D07 Slip into ambient temperature high point -10~10°C TEMP1
1108 03/16/06 454 D08 Slip into ambient temperature low point -30~10°C TEMP1
1109 03/16/06 455 D09 Whether enable sliding defrost (0-no/1-yes) DIGI1
1110 03/16/06 456 D10 Whether enable auxiliary electric heating during defrosting 0~1 DIGI1
1111 03/16/06 457 D11 Defrost frequency 0-90Hz DIGI1
1112 03/16/06 458 Reserved
1113 03/16/06 459 Reserved
1114 03/16/06 45A Reserved
1115 03/16/06 45B Reserved
1116 03/16/06 45C Reserved
1117 03/16/06 45D Reserved
1118 03/16/06 45E Reserved
1119 03/16/06 45F Reserved
1120 03/16/06 460 Reserved
1121 03/16/06 461 Reserved
1122 03/16/06 462 Reserved
1123 03/16/06 463 Reserved
1124 03/16/06 464 Reserved
1125 03/16/06 465 Reserved
1126 03/16/06 466 Reserved
1127 03/16/06 467 E01 EEV adjustment 0~1 (0-manual/1-auto) DIGI1
1128 03/16/06 468 E02 EEV heating target overheat -10~10°C TEMP1