– 8 –
Model SCM Air to Water Heat Pump — Installation, Operation & Maintenance Manual
Section 3: Specications and Ratings (continued)
Heat Pump SCM036 Series
PERFORMANCE
4.00
3.00
2.00
1.00
10,000
15,000
20,000
25,000
30,000
35,000
40,000
45,000
15 20 25 30 35 40 45 50
SCM-036 HEAT ING PERFORMANCE
120
110
100
Coefficient of Performance
OUTDOOR AMBIENT TEMPERATURE, °F
All data based upon pure water @10.0 GPM
SupplyWater
Temp °F
SCM-036 Heating Operation SCM-036 Cooling Operation
Supply
Water
Temp °F
Ambient
Temp °F
Capacity
BTU/hr
Water DP
ft WC
Watts COP
Supply
Water
Temp °F
Ambient
Temp °F
Capacity
BTU/hr
Water DP
ft WC
Watts COP
100
17 23,397 12.0 2,742 2.50
42
82 36,225 12.0 3,019 3.20
32 33,075 12.0 2,801 3.46 95 33,872 12.0 3,528 2.40
47 42,754 12.0 3,008 4.16 105 30,579 12.0 4,497 1.70
110
17 21,718 12.0 3,190 1.99
44
82 38,500 12.0 3,208 3.60
32 30,703 12.0 3,258 2.76 95 36,000 12.0 3,750 2.50
47 39,687 12.0 3,499 3.32 105 32,500 12.0 4,100 1.80
120
17 20,160 12.0 3,710 1.59
47
82 42,070 12.0 3,825 3.80
32 28,500 12.0 3,790 2.20 95 39,338 12.0 4,522 2.80
47 36,840 12.0 4,070 2.65 105 35,514 12.0 5,822 2.00
All data based upon pure water @ 10.0 GPM
1.0
2.0
3.0
4.0
80 85 90 95 100 105 110
SCM-036 COOLING PERFORMANCE
42
44
47
15,000
20,000
25,000
30,000
35,000
40,000
45,000
COOLING CAPACITY, BTU/hr
Coefficient of Performance
OUTDOOR AMBIENT TEMPERATURE, °F
All data based upon pure water @10.0 GPM
SupplyWater
Temp °F
SCM-036 Heating Performance
SCM-036 Cooling Performance